IFM AL1325 handleiding
Handleiding
Je bekijkt pagina 45 van 121

IO-Link master with EtherNet/IP interface AL1325
45
9.2.8 Fieldbus: Configuring the EtherNet/IP interface
For communication with the EtherNet/IP network, the EtherNet/IP interface must be configured.
Substructure: fieldbussetup
Available data points:
Name Description Values Access
../network/dhcp Status of the DHCP client • 0: Static IP address:
• 1: DHCP (Dynamic Host
Configuration Protocol)
• 2: BOOTP (Bootstrap Protocol)
rw
1
../network/ipaddress IP address of the Ethernet interface: e.g. 192.200.0.100
• 192.168.1.250 (Default)
rw
1
2
../network/subnetmask Subnet mask of the network segment e.g. 255.255.192.0
• 255.255.255.0 (Default)
rw
1
2
../network/ipdefaultgateway IP address of the network gateway e.g. 192.200.63.1
• 0.0.0.0 (Default)
rw
1
2
../network/macaddress MAC address of the Ethernet interface e.g. 00:02:01:0E:10:7C ro
3
../hostname EtherNet/IP hostname e.g. alxx2x rw
1
../fieldbusfirmware Firmware of the fieldbus e.g. ro
3
../connectionstatus Status of the fieldbus connection • 0: Not connected
• 1: Connected
ro
3
1
Read and write
2
The parameter can only be changed if no connection to the fieldbus controller is active
3
Read only
Applicable services:
Name Description
../network/setblock Write all values of the substructure blockwise
u Change the parameters in the substructure network only block by block with the service
setblock!
9.2.9 Fieldbus: Setting the EtherNet/IP configuration mode
The device supports the EtherNet/IP configuration modes "Top-Down Mode" and "Independent Mode".
Substructure: fieldbussetup/configuration
Available data points:
Name Description Value range Access
../independentmode Configuration mode • 0: Independent mode off
• 1: Independent mode on
rw
1
2
../explicitmodepd Connection types (Input Assembly, Out-
put Assembly)
• 0: Explicit Process Data Mode off
• 1: Explicit Process Data Mode with
IO-Link I/O + Acyclic + Diag
• 2: Explicit Process Data Mode with
IO-Link I/O + Acyclic
• 3: Explicit Process Data Mode with
IO-Link I/O
rw
1
2
../processdataconfiguration Length of the process data • 0: 2 bytes input 2 bytes output
• 1: 4 bytes input 4 bytes output
• 2: 8 bytes input 8 bytes output
• 3: 16 bytes input 16 bytes output
• 4: 32 bytes input 32 bytes output
rw
1
2
Bekijk gratis de handleiding van IFM AL1325, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | IFM |
| Model | AL1325 |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |
| Grootte | 9966 MB |