IFM AL1325 handleiding
Handleiding
Je bekijkt pagina 41 van 121

IO-Link master with EtherNet/IP interface AL1325
41
{
"cid":11,
"code":10,
"adr":"setasync/datachanged/subscribe",
"data":{
"datatosend":["setasync"],
"callback":http://example.org:8080/dump
}
}
9.2.4 IoT: Configuring access rights
The device can be integrated in parallel into a fieldbus environment and into an IT network structure
for IIoT applications (“Y-path”).
Changes to the Gateway: Resetting, rebooting and localising the device (Ò/58) data point
will only take effect after the device has been restarted.
Substructure: iotsetup
Available data points:
Name Description Value range Access
.../accessrights Access rights to the device • 0: Fieldbus + IoT (default):
– Fieldbus and ifm IoT Core have read and write
access rights to parameters and process data
– Fieldbus and ifm IoT Core have read and write
access rights to parameters and process data
• 1: Fieldbus + IoT (read only):
– Fieldbus has read and write access rights to
parameters and process data
– Fieldbus has read access rights to events / alarms
– ifm IoT Core has read access rights to parameters,
process data and events / alarms
• 3: IoT only
– ifm IoT Core has read and write access rights to
parameters and process data
– ifm IoT Core has read access rights to events /
alarms
– Fieldbus has no access rights
rw
1
1
Read and write
Bei der Parametrierung der Zugriffsrechte mit dem ifm IoT Core folgende Hinweise beachten:
• If the access rights in the fieldbus projection software and the parameter setting software are set to
the [Fieldbus + IoT] value, the parameter values set on the fieldbus side always apply.
• For exclusive access to the device via the parameter setting software, set the access rights to the
[IoT only] value and set the access rights to [Keep settings] in the fieldbus projection software.
• Wenn die Zugriffsrechte im ifm IoT Core auf den Wert [Fieldbus + IoT (read only)] eingestellt sind,
dann können die Zugriffsrechte über den ifm IoT Core nicht mehr geändert werden. To regain write
access with the parameter setting software, set the access rights in the fieldbus projection software
to the [Fieldbus + IoT] value.
9.2.5 IoT: Configuring IP settings
Substructure: iotsetup/network
Available data points:
Bekijk gratis de handleiding van IFM AL1325, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.