IFM AL1325 handleiding

121 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 26 van 121
AL1325 IO-Link master with EtherNet/IP interface
26
Name Description Value range Access
Vendor ID Vendor ID of the IO-Link device to be
validated against
e.g., 310: ifm electronic gmbh rw
1
2
Device ID Device ID of the IO-Link device to be
validated against
e.g., 1129: TCC501 (ifm temperature
sensor)
rw
1
2
1
Read and write
2
Parameter only available if operating mode pin 4 (US) = IO-Link and IO-Link device is connected to the port
To configure the device validation and the backup / restore of parameter values:
Requirements:
ü The parameter setting software has been started.
ü The connection to the device has been established.
ü The detailed view of the device is active.
ü Operating mode of pin 4 of the port is “IO-Link”.
u Select the [Port x] > [IO-Link] menu (x = 1…4).
w The menu page shows the current settings.
u Set the parameters for device validation and backup / restore of parameter values.
u Optional: Enter the vendor ID and device ID.
u Save the changes on the device.
w Device validation and backup / restore of parameter values have been configured.
9.1.11 Ports: Setting the cycle time
In der Betriebsart "IO-Link" kann zusätzlich die Zykluszeit des Ports eingestellt werden.
Available parameters:
Parameter Description Value range Access
Cycle time actual Current cycle time between the IO-Link
master and the IO-Link device (value in
µs)
0: best possible cycle time
132800: 132800µs
ro
1
2
Cycle time preset Cycle time between the IO-Link master
and the IO-Link device (value in µs)
0: best possible cycle time
1: 1 µs
132800: 132800µs
rw
3
2
Bit rate Transmission rate between the IO-Link
master and the IO-Link device
COM1: 4.8 kbaud
COM2: (38.4 kbaud)
COM3: 230.4kbaud
ro
1
2
1
Read only
2
Parameter only available if operating mode pin 4 (US) = IO-Link and IO-Link device is connected to the port
3
Read and write
Requirements:
ü The parameter setting software has been started.
ü The connection to the device has been established.
ü The detailed view of the device is active.
ü Operating mode of pin 4 of the port is “IO-Link”.
u Select the [Port x] > [IO-Link] menu (x = 1…4).
Setting the cycle time
u Write the changed values to the device.
w Zykluszeit des IO-Link Ports ist eingestellt.