IFM AL1325 handleiding
Handleiding
Je bekijkt pagina 26 van 121

AL1325 IO-Link master with EtherNet/IP interface
26
Name Description Value range Access
Vendor ID Vendor ID of the IO-Link device to be
validated against
e.g., 310: ifm electronic gmbh rw
1
2
Device ID Device ID of the IO-Link device to be
validated against
e.g., 1129: TCC501 (ifm temperature
sensor)
rw
1
2
1
Read and write
2
Parameter only available if operating mode pin 4 (US) = IO-Link and IO-Link device is connected to the port
To configure the device validation and the backup / restore of parameter values:
Requirements:
ü The parameter setting software has been started.
ü The connection to the device has been established.
ü The detailed view of the device is active.
ü Operating mode of pin 4 of the port is “IO-Link”.
u Select the [Port x] > [IO-Link] menu (x = 1…4).
w The menu page shows the current settings.
u Set the parameters for device validation and backup / restore of parameter values.
u Optional: Enter the vendor ID and device ID.
u Save the changes on the device.
w Device validation and backup / restore of parameter values have been configured.
9.1.11 Ports: Setting the cycle time
In der Betriebsart "IO-Link" kann zusätzlich die Zykluszeit des Ports eingestellt werden.
Available parameters:
Parameter Description Value range Access
Cycle time actual Current cycle time between the IO-Link
master and the IO-Link device (value in
µs)
• 0: best possible cycle time
…
• 132800: 132800µs
ro
1
2
Cycle time preset Cycle time between the IO-Link master
and the IO-Link device (value in µs)
• 0: best possible cycle time
• 1: 1 µs
…
• 132800: 132800µs
rw
3
2
Bit rate Transmission rate between the IO-Link
master and the IO-Link device
• COM1: 4.8 kbaud
• COM2: (38.4 kbaud)
• COM3: 230.4kbaud
ro
1
2
1
Read only
2
Parameter only available if operating mode pin 4 (US) = IO-Link and IO-Link device is connected to the port
3
Read and write
Requirements:
ü The parameter setting software has been started.
ü The connection to the device has been established.
ü The detailed view of the device is active.
ü Operating mode of pin 4 of the port is “IO-Link”.
u Select the [Port x] > [IO-Link] menu (x = 1…4).
Setting the cycle time
u Write the changed values to the device.
w Zykluszeit des IO-Link Ports ist eingestellt.
Bekijk gratis de handleiding van IFM AL1325, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | IFM |
| Model | AL1325 |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |
| Grootte | 9966 MB |







