AL1325 IO-Link master with EtherNet/IP interface
24
Parameter Description Value range Access
Process data mode Enable / disable explicit PD mode and
select the process data to be transmit-
ted (connection type)
• Explicit process data mode off: Explicit
PD mode disabled
• Explicit process data mode with IO-Link
I/O + Acyclic + Diag: Explicit PD mode
enabled -- IO-Link inputs/outputs,
acyclic data and diagnostic data is
transmitted
• Explicit process data mode with IO-Link
I/O + Acyclic: Explicit PD mode
activated -- IO-Link inputs/outputs and
acyclic data is transmitted
• Explicit process data mode with IO-Link
I/O: Explicit PD mode enabled -- IO-
Link inputs/outputs are transmitted
rw
1
3
Process data length Length of process data (per IO-Link
port)
• 2 bytes input 2 bytes output: 2 bytes
input data, 2 bytes output data
• 4 bytes input 4 bytes output 4 bytes
input data, 4 bytes output data
• 8 bytes input 8 bytes output 8 bytes
input data, 8 bytes output data
• 16 bytes input 16 bytes output 16 bytes
input data, 16 bytes output data
• 32 bytes input 32 bytes output 32 bytes
input data, 32 bytes output data
rw
1
2
Swap Swap the order of the bytes in the data
word of the process data
• off: as Array of Bytes
• on: as Integer16 value; during an
update of the process data, the bytes
are exchanged
rw
1
2
1
Read and write
2
The parameter can only be changed if no connection to the fieldbus controller is active
3
Parameters can only be changed in "Independent" configuration mode
Requirements:
ü The parameter setting software has been started.
ü The connection to the device has been established.
ü The detailed view of the device is active.
w The menu page shows the current settings.
u Set the configuration mode.
u Optional: Select connection type.
u Set arrangement of the bytes in the process data.
u Save the changes on the device.
w EtherNet/IP configuration mode is set.
9.1.9 Ports: Setting the operating mode Pin 4 (US)
Pin 4 of ports X01...X04 supports the following operating modes:
• Disabled: No data transmission at pin 4 (C/Q) of the port
• Digital input: Binary input signal at pin 4 (C/Q) of the port
• Digital output: Binary output signal at pin 4 (C/Q) of the port
• IO-Link: IO-Link data transmission via pin 4 (C/Q) of the port
The set operating mode must match the operating mode of the device connected to the port (sensor,
actuator, IO-Link device).
Available parameters: