AE3400 IIoT controller
18
7 Operating and display elements
7.1 LEDs
2 3
45
6
7
1
1: Status: SYS
2: Status: APP
3: Status: PRG
4: Ethernet: ACT LNK (port eth3)
5: Ethernet: ACT LNK (port eth2)
6: Ethernet: ACT LNK (port eth1)
7: Ethernet: ACT LNK (port eth0)
The ACT (left) and LNK (right) status LEDs are located behind the elongated light domes of the
Ethernet ports.
7.1.1 Status
SYS LED APP LED PRG LED
Description
Col-
our
State
Col-
our
State Colour State
- Off - Off - Off Supply voltage not applied or supply voltage too low
Green Flashes
(0.5Hz)
- Off - Off Device starts
Green On Green On -
1
-
1
CODESYS runtime started
Green On - Off - Off CODESYS runtime stopped or no application
Green On Yel-
low
Flashes
(0.5Hz)
-
1
-
1
CODESYS Development System connected
Green On Red Flashes
(2Hz)
- Off CODESYS application error
Yellow Flashes
(0.5Hz)
- Off - Off Firmware being updated
Yellow On - Off - Off Recovery System in standby
Red Flashes
(2Hz)
- Off - Off Error (firmware error, error during firmware update or power
supply error, etc.)
1
Behaviour of LED, freely configurable in CODESYS application (Ò programming manual)
7.1.2 Ethernet
LED Description Colour State Description
LNK Status of the connection - Off No Ethernet connection
Green On Ethernet connection established
ACT Status of the data transmis-
sion
- Off No data transmission
Yellow Flashes Data transmission
7.2 Function key
The device provides the following function key: