Huawei SUN2000-25KTL-M5 handleiding

97 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 42 van 97
Table 5-3 Signal denitions
Pin Denition Function Description
1 GND Ripple control GND port for the DIN1 to
DIN5 signals
2 DIN1 Dry contact for grid
scheduling
3 DIN2
4 DIN3
5 DIN4
6 DIN5 Rapid shutdown signal+ For the rapid shutdown DI
signal or connecting to the
signal cable of an NS
protective device
7 GND GND -
8 - - -
9 485A1 RS485A1 dierential
signal+
For inverter cascading or
connecting to the RS485
signal port of a
SmartLogger
10 485B1 RS485B1 dierential
signal–
11 485A2 RS485A2 dierential
signal+
Connecting to the RS485
signal port of a power
meter
12 485B2 RS485B2 dierential
signal–
Procedure
Step 1 Route the cables through the junction box and prepare cable terminals.
NO TICE
The cable stripping length must meet the requirements. Otherwise, the
airtightness and waterproof performance of the device may be aected.
SUN2000-(12KTL-25KTL)-M5 Series
User Manual 5 Electrical Connections
Issue 01 (2022-06-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 36