INSTALLATION MANUAL
41
MULTI SPLIT IX21D5MULTI SPLIT IX21D5
12. Install the equipment in accordance with the regulations for electrical installations in your country.
WARNING
13. An all-pole disconnection device that has a minimum separation of 3 mm between poles and a leakage
current that can exceed 10 mA, the residual current device (RCD), must be incorporated into the xed
wiring, following wiring regulations. with a nominal residual operating current not exceeding 30 mA.
14. Disconnection of the appliance must be incorporated with an all-pole disconnection device in the xed
wiring in accordance with wiring regulations
15. Any person involved in the maintenance or repair of a refrigerant circuit must have a current valid
certicate issued by an industry-accredited testing body, certifying their tness to handle refrigerants
safely in accordance with an testing specication recognized by the industry. the industry..
16. Reviews will only be carried out in the manner recommended by the equipment manufacturer..
17. Maintenance and repairs requiring the assistance of other qualied personnel should be performed
under the supervision of the person competent in the use of ammable refrigerants.
18. The appliance must be stored to prevent mechanical damage.
19. Keep ventilation openings free of obstructions..
20. Do not puncture or burn the device.
21. When moving or relocating the air conditioner, consult experienced service technicians for disconnection
and reinstallation of the unit..
22. In certain functional environments, such as kitchens, server rooms, etc., it is recommended
The use of specially designed air conditioning equipment is strongly encouraged..
23. The disconnection of the plug must be carried out in such a way that an operator can verify, from any of
the points to which he has access, that the plug remains disconnected..
24. If this is not possible, due to the design of the appliance or its installation, a disconnection with a locking
system in the isolated position must be provided..
CAREFUL
If units have an auxiliary electric heater, do not install them within 1 meter (3 feet) of any combustible
materials.
Do not install the unit in a location that may be exposed to combustible gases. If combustible gas
accumulates around the equipment, it may cause a re.
Do not use your air conditioner in a room with high humidity, such as a bathroom or laundry room. Too much
exposure to water can cause electrical components to short out.
1. The product must be properly grounded at the time of installation, or electric shock may occur.
2. Install the drain pipe following the instructions in this manual. Improper drainage can cause ooding in
your home and damage to your property.