3. Undercounter and Worktop Freezers
Heated Defrost: Freezers utilize a temperature or time initiated heated defrost.
• Temperature Initiated: When the defrost thermistor is at or below -31°F (-35°C),
defrost starts.
• Time Initiated: Once the 5-hr. Cumulative Compressor Run Timer terminates,
defrost starts.
• Time Initiated: Once the 4-hr. Continuous Compressor Run Timer terminates,
defrost starts.
• When defrost initiates, the maximum 1-hr. defrost timer starts. Defrost heater
energizes, compressor, condenser fan motor, and evaporator fan motor
de-energize.
• When the defrost thermistor reaches 55°F (12.7°C), or the maximum 1-hr. defrost
timer terminates, defrost terminates. Defrost heater de-energizes. 3-min. drip
time starts. Once the 3-min. drip timer terminates the compressor, condenser fan
motor, and evaporator fan motor energize.
The maximum defrost time is 1 hr.
E. Alarm Safety
The alarm signal is designed to protect the appliance and food product. This alarm gives
notication that the appliance is operating out of acceptable parameters. Should the
alarm occur, follow the instructions in the table below to address the alarm.
CONTROL MODULE LED ALARM OPERATION
LEDs LED OPERATION
R G B
ON ACTIVE ALARM (cooling cycle)
ACTIVE ALARM (defrost cycle)
The Active alarm initiated by of an out-of-position
thermistor, loose thermistor connection on the control
module, cooling cycle issue, defrost cycle issue, or faulty
component. Consult the service manual for further details.