39
D. Defrost
DANGER
Risk of Fire or Explosion Flammable Refrigerant Used
• Do not use mechanical devices to defrost.
• Do not puncture refrigerant tubing. Risk of re or explosion due to puncture of
refrigerant tubing; follow handling instructions carefully.
Risque De Feu Ou D'Explosion Le Frigorigène Est Inammable
• Ne pas utiliser d'appareils mécaniques pour dégivrer le réfrigérateur.
• Ne pas perforer la tubulure contenant le frigorigène. Risque de feu ou d'explosion
si la tubulure contenant le frigorigène est perforée; suivre les instructions de
manutention avec soin.
1. Undercounter and Worktop Refrigerators
Off-Cycle Defrost: Undercounter and worktop refrigerators defrost naturally between run
cycles and have a temperature or time initiated defrost cycle.
Temperature Initiated: When the defrost thermistor is at or below -4°F (-20°C),
defrost starts.
Time Initiated: Once the 5-hr. Cumulative Compressor Run Timer terminates,
defrost starts.
Time Initiated: Once the 4-hr. Continuous Compressor Run Timer terminates,
defrost starts.
When defrost initiates, the maximum 1-hr. defrost timer starts. Compressor and
condenser fan motor de-energize. Evaporator fan motor remains energized.
When the defrost thermistor reaches 45°F (7.2°C), or the maximum 1-hr. defrost
timer terminates, defrost terminates. Evaporator fan motor remains energized and
compressor and condenser fan motor energize.
The maximum defrost time is 1 hr.
2. Prep Table Refrigerators
Heated Defrost: Prep table refrigerators utilize a time initiated heated defrost.
Temperature Initiated: When the defrost thermistor is at or below -31°F (-35°C),
defrost starts.
Time Initiated: Once the 5-hr. Cumulative Compressor Run Timer terminates,
defrost starts.
Time Initiated: Once the 4-hr. Continuous Compressor Run Timer terminates,
defrost starts.
When defrost initiates, the maximum 1-hr. defrost timer starts. Defrost heater
energizes, compressor, condenser fan motor, and evaporator fan motor
de-energize.
When the defrost thermistor reaches 46°F (7.7°C), or the maximum 1-hr. defrost
timer terminates, defrost terminates. Compressor, condenser fan motor, and
evaporator fan motor energize.
The maximum defrost time is 1 hr.