E. Defrost
DANGER
Risk of Fire or Explosion Flammable Refrigerant Used
• Do not use mechanical devices to defrost.
• Do not puncture refrigerant tubing. Risk of re or explosion due to puncture of
refrigerant tubing; follow handling instructions carefully.
Risque De Feu Ou D'Explosion Le Frigorigène Est Inammable
• Ne pas utiliser d'appareils mécaniques pour dégivrer le réfrigérateur.
• Ne pas perforer la tubulure contenant le frigorigène. Risque de feu ou d'explosion si la
tubulure contenant le frigorigène est perforée; suivre les instructions de manutention
avec soin.
1. Automatic Defrost
Defrost is a time/temperature initiated, temperature terminated heated defrost.
• Defrost Initiation: When the appliance is plugged in, the 6 hr. defrost timer
starts. Once the 6 hr. defrost timer terminates, the rail control module checks the
defrost thermistor for defrost initiation temperature of 41°F (5°C) or below. If the
defrost thermistor is not at or below 41°F (5°C), the rail control module continues
in the cooling mode. If defrost thermistor is at or below 41°F (5°C), defrost
initiates. Ifenergized, the compressor, rail fan motor(s), and cabinet fan motor(s)
de-energize. Defrost heater energizes, cabinet display cooling icon turns off, defrost
icon turns on, and "dEF" is displayed.
Note: To manually reset the 6-hr. defrost timer, initiate a manual defrost then
terminate using the same procedure as initiating a manual defrost.
See "II.E.2. Manual Defrost" below.
• Cabinet Display During Defrost: "dEF" is displayed. The cooling (cabinet fan
motor) icon turns off and the defrost icon turns on. The defrost icon and "dEF" are
displayed for 30 min. Note: Cabinet fan motor(s) are locked out during the 30-min.
defrost icon and "dEF" display time. The compressor and rail fan motor(s) are
controlled separately by the rail thermistor and rail control module.
• Defrost Termination: After the 5-min. minimum defrost timer terminates and the
defrost thermistor warms to 41°F (5°C), the rail control module terminates defrost
and resets the 6 hr. defrost timer. Note: Cabinet display is not affected by the rail
defrost thermistor temperature and continues to show "dEF" until the 30-min. "dEF"
display timer terminates.
• The compressor and rail fan motor(s) energize 3-min. after defrost termination
(drip time). Note that the 3 min. rail fan motor delay time is a maximum; if the
defrost thermistor cools to 36°F (2.2°C) before the 3 min. rail fan motor delay timer
terminates, the rail fan motor(s) energize.