Start-up
The “5 safety rules” to be used:
Disconnect from mains
Secure against restart
Check for absence of voltage
Earth and short circuit
Cover or cordon off neighbouring
live parts
Selection of suitable tools, mea-
suring equipment and, if necessary,
personal protective equipment;
Evaluation of measuring results;
Selection of electrical installation
material for safeguarding shut-off
conditions;
IP protection types;
Installation of electrical installation
material;
Type of supply network (TN system,
IT system, TT system) and the re-
sulting connection conditions (clas-
sic zero balancing, protective earth-
ing, required additional measures,
etc.).
Permitted cable cross sections for con-
necting to the device are:
rigid and flexible cable (without
ferrule) 0.2 - 1.5 mm², flexible cable
(with ferrule) 0.25 - 1.5 mm²
5.2 Assembly and installation
Proceed as follows to install the device
on a DIN rail:
Disconnect the power distribution
panel and cover any live parts, if re-
quired.
Remove the cover from the power
distribution panel.
Open the bus cable adapter by gen-
tly pressing the spring clips at the
sides.
E
Figure 3
Strip the bus connection cable by
30 mm.
Strip the individual wires by 8 mm.
Connect the wires to the terminal
according to the following table.
Function EIB cable HmIPW cable
+ (24 VDC)
Red
- (GND,
Earth)
Black
A (RS-485)
White
B (RS-485)
Yellow
When using shielded cables, the
shield (supporting wire) must be
placed on “–” (= Earth).
5