Functions and Control
Enhanced defrost mode
Remote control:ODU in heating or shut down state, the user set high fan speed, 30°C, and press the sleep button 6
times within 5 seconds,when the buzzer sounds 3, it enter the manual defrost mode. The method is the same as the
heating defrost.
Wired controller mode:When it receive the wired controller enforced defrost signal, it will enter the defrost mode.
Anti-cold air control during defrosting
IDU will immediately stops the fan after receiving the defrosting signal.
After defrosting, the IDU fan runs according to anti-cold air.
ECO function
1. Entry condition
In the startup state, the IDU receive the remote controller, wired controller, and ECO button signal to realize the ECO
function(or via app). Temperature compensation is only compensated once upon entry, and the newly set temperature
is no longer compensated during ECO operation.
2. Function description
ECO functions are e󰀨ective for both cooling and heating modes.
2.1 In cooling mode, the user press the ECO button (or via APP) to enter the ECO function, and set the temperature 2
° F (or 1°C) higher than the current set temperature (The default is °F adjustment), which can be adjusted in the APP;
The adjusted set temperature shall not exceed the temperature range in 2.3.
2.2 In heating mode, the user presses the ECO button (or via APP) to enter the ECO function, and set the temperature
2 ° F (or 1°C) lower than the current set temperature (The default is °F adjustment), which can be adjusted in the APP;
The adjusted set temperature shall not exceed the temperature range in 2.3
2.3 After entering ECO mode, the set temperature range of cooling and heating is 60 ° F to 86 ° F, and the operating
range of the set temperature can be reduced through the APP (example: Set temperature range from 60 ° F-86 ° F to
70 ° F-80 ° F). Note: The maximum set temperature≥the minimum set temperature,and the displayed set temperature
changes together
2.4 In cooling mode, during ECO mode, when the set temperature reaches, via APP the user can stop the IDU fan (the
ducted will reach the temperature and stop the air by default, and other IDUs won’t.
2.5 The di󰀨erent Settings of ECO functions should be stored in the IDU. The settings remain the same the next time the
unit enter eco mode.(GEA needs to create an ERD and transmit all the ECO parameters excluding the upper and lower
limits of the temperature).
2.6 Exit condition
In ECO mode, the IDU can exit the ECO mode only by pressing the ECO button or exiting from the APP.