2> Disconnect the DC switches and the AC breakers on the grid side, generator side
and the battery side.
1> Ensure the grid voltage and the grid frequency are within the acceptable range;
Preparation:
AC circuit breaker needs to be installed on the grid side, ensuring a safe
disconnection between the WIT Inverter and the upstream input when an
exception occurs.
The circuit breaker on the AC side:
1. Recommended AC breaker specifications for WIT 29.9-50K-XHU models
Device type
Rated voltage of the circuit
breaker
Rated current of the circuit
breaker
WIT 29.9K-XHU
400V
150A
WIT 30K-XHU
400V
150A
WIT 36K-XHU
400V
150A
WIT 40K-XHU
400V
200A
WIT 50K-XHU
400V
250A
2. Recommended load breaker specifications for WIT 29.9-50K-XHU models
Device type
Rated voltage of the circuit
breaker
Rated current of the circuit
breaker
WIT 29.9K-XHU
400V
80A
WIT 30K-XHU
400V
80A
WIT 36K-XHU
400V
80A
WIT 40K-XHU
400V
100A
WIT 50K-XHU
400V
125A
3. Recommended bypass breaker specifications for WIT 29.9-50K-XHU models
Device type
Rated voltage of the circuit
breaker
Rated current of the circuit
breaker
WIT 29.9K-XHU
400V
80A
WIT 30K-XHU
400V
80A
WIT 36K-XHU
400V
80A
WIT 40K-XHU
400V
100A
WIT 50K-XHU
400V
125A
4. Recommended Gen breaker specifications for WIT 29.9-50K-XHU models
Device type
Rated voltage of the circuit
breaker
Rated current of the circuit
breaker
WIT 29.9K-XHU
400V
150A
WIT 30K-XHU
400V
150A
WIT 36K-XHU
400V
150A
WIT 40K-XHU
400V
200A
WIT 50K-XHU
400V
250A
NOTE:
For the PCS to operate in Smart Load mode, select the appropriate AC breaker
based on the smart load power.
3231
6.2 Connection on the AC Side
Ÿ Only qualified and trained electrical technicians are allowed to
perform operations. Technicians must observe instructions in
this manual and local regulations.
Ÿ Before connecting cables, ensure that the DC switches on the
WIT Inverter are OFF. Turn off the switches and breakers on the
GRID side, GEN side and the battery side. Otherwise, the high
voltages of the WIT Inverter may result in electric shocks.
Ÿ Do not place inflammable and explosive materials around the
WIT Inverter.
Ÿ High voltages may cause electric shocks and serious injury.
Please do not touch the inverter in operation.
Ÿ Please do not connect loads between the WIT Inverter and the
circuit breaker.
Ÿ If the cable is thick, do not wiggle the cable after tightening the
cable terminals. Otherwise, the loose connection may cause
overheating that will damage the device. Ensure that the
terminals are properly connected before starting the WIT
Inverter.
Ÿ Each WIT Inverter must be equipped with a separate AC circuit
breaker. Multiple WIT Inverters cannot connect to the same AC
circuit breaker (not applicable to off-grid mode).
Ÿ Upon completion of the AC wiring, remember to seal the water-
proof silicone mat with the fireproof mud in order to ensure
good waterproof performance.
DANGER
WARNING