39
14
Solar charger stops due
to overload
Beep once every second
15
Parallel input utility grid
different
Beep once every second
16
Parallel input phase error
Beep once every second
17
Parallel output phase loss
Beep once every second
19
Battery disconnect
Beep once every second
51
PV Over current or surge
Beep once every second
58
AC output low voltage
Beep once every second
Trouble Shooting
Problem
LCD/LED/Buzzer
Explanation / Possible cause
What to do
Unit shuts down
automatically
during startup
process.
LCD/LEDs and buzzer
will be active for 3
seconds and then
complete off.
The battery voltage is too low
(<1.91V/Cell)
1.
Re-charge battery.
2.
Replace battery.
No response after
power on.
No indication.
1.
The battery voltage is far
too low. (<1.4V/Cell)
2.
Battery polarity is
connected reversed.
1.
Check if batteries and
the wiring are connected
well.
2.
Re-charge battery.
3.
Replace battery.
Buzzer beeps
continuously and red
LED is on. (Fault
code)
Buzzer beeps once
every second, and
red LED is flashing.
(Warning code)
Warning code 01
Fan Warning
1. Check whether all fans are
working properly.
2.Replace the fan.
Fault code 02
Internal temperature of
component is over 90°C.
Check if the air flow of the
unit is blocked or the
ambient temperature is too
high.
Fault code 03
Battery is over-charged.
Return to repair center.
The battery voltage is too high.
Check if spec and quantity
of batteries are meet
requirements.
Fault code 04
The battery voltage is too low.
1. Measure battery voltage in
DC input.
2. Check battery SOC in LCD
when use Li battery
3. Recharge the battery.
Fault code 05
Output short circuited.
Check if wiring is connected
well and remove abnormal
load.
Fault code 06/58
Output abnormal (Inverter voltage
below than 180Vac or is higher
than 290Vac)
1.
Reduce the connected
load.
2.
Return to repair center
Fault code 07
Overload error. The inverter is
overload 101% and time is
up.
Reduce the connected load by
switching off some
equipment.