Note: This function is only applicable to stand-alone mode, and cannot be used in parallel mode.
2. Overload protection:
2.1 When load current < max AC input current +max inverter mode current, It will use Ac bypass mode and inverter
mode to power connected load continuously maximum at 6KW@3000W( 12KW@6000W).
When battery voltage drop to setting value at program 90, battery will not discharge in SUB mode, but only use AC
input current to power connected load. inverter will say 07 overload error code if load current is bigger than max AC
input current at this time.
2.2 When load current>max AC input current +max inverter mode current ,inverter says 07 overload error code after 10
seconds.
Fault Code
Fault Code
Fault Event
Icon on
02
Inverter Over temperature
03
Battery voltage is too high
04
Battery voltage is too low
05
Output short circuited
06
Output voltage is abnormal. Output voltage is too
high.
07
Overload time out
20
BMS communication error
51
Over current or surge
56
MOS overcurrent
60
Negative power fault
80
CAN fault
81
Host loss
Warning Code
Warning
Code
Warning Event
Audible Alarm
Icon flashing
01
PV Fan is not working/ Inverter
Fan is not working
Beep once every second
02
PV Over temperature
Beep once every second
04
Low battery
Beep once every second
07
Overload
Beep once every second
13
Solar charger stops due to
high PV voltage
Beep once every second