WARNING:
Be sure that AC power source is disconnected before attempting to hardwire it to the unit.
CAUTION: Important
Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause
utility short-circuited when these inverters are worked in parallel operation.
PV Connection
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter
and PV modules.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It’ very important for system safety and efficient operation to use appropriate cable for PV module
connection. To reduce risk of injury, please use the proper recommended cable size as below.
Model
Wire Size
Torque value
SPF 3500TL HVM-Pro
1 * 12 AWG
1.2-1.6 Nm
SPF 5000TL HVM-Pro
1 * 12 AWG
1.2-1.6 Nm
PV Module Selection:
When selecting proper PV modules, please be sure to consider below parameters:
1.
Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
2.
Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
Please follow below steps to implement PV module connection:
1. Insert PV panel positive and negative cables into MC4 terminal, then connect positive pole(+)of connection
cable to positive pole(+)of PV input connector, connect negative pole(-)of connection cable to negative
pole(-) of PV input connector.
2. Make sure the wires are securely connected.
INVERTER MODEL
SPF 3500TL HVM-Pro
SPF 5000TL HVM-Pro
Max. PV Array Open Circuit Voltage
450Vdc
Start-up Voltage
150Vdc
PV Array MPPT Voltage Range
120Vdc~430Vdc
CAUTION: Appliances such as air conditioner are required at least 2~3 minutes to restart because it’s
required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and
recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage,
please check with manufacturer of air conditioner that if it’s equipped with time-delay function before
installation. Otherwise, this off grid solar inverter will trigger overload fault and cut off output to protect your
appliance but sometimes it still causes internal damage to the air conditioner.