10 Gossen Metrawatt GmbH
4.2 Measuring Loop Impedance (Z
L
-
PE
)
ATTENTION!
!
Single-Phase Mains Connection
The phase must be connected to L1
for single-phase mains connection.
4.2.1 Measuring Loop Resistance with the
PROFITEST MTECH+ IQ or
PROFITEST
MXTRA IQ
Preparing for Measurement
➭ Connect the test instrument’s test plug
to the PRO-SCHUKO plug insert.
➭ Disconnect the system from all sources
of voltage before connecting the mea-
suring points to the test adapter.
➭ Connect the system to sockets L1, L2,
L3, N and PE.
➭ Switch the system on.
Performing the Measurement
ATTENTION!
!
Insulation test voltage may not ex-
ceed 500 V.
➭ Perform the measurement as described
in the operating instructions for the re-
spective test instrument:
PROFITEST MTECH+ IQ: sections 5.8 and 9
PROFITEST MXTRA IQ: sections 5.8 and 9
NOTE!
Measurement of loop impedance Z
L
-
PE
with the PROFITEST MTECH+ IQ and/
or PROFITEST MXTRA IQ is conducted
with sine (full-wave) and 15 mA sine.
Measurements with DC and halve-
wave are not possible.
Overview of Connected Conductors
The red illuminated LEDs in the connections
overview indicate the respectively connected
conductors.
Continuity, Z
L
-
PE
4.2.2 Measuring Loop Impedance with the
PROFITEST PRIME
Preparing for Measurement
➭ Using the corresponding test probes,
connect the test instrument to the L, N
and PE sockets at the test adapter.
➭ Disconnect the system from all sources
of voltage before connecting the mea-
suring points to the test adapter.
➭ Connect the system to sockets L1, L2,
L3, N and PE.
➭ Switch the system on.
Performing the Measurement
ATTENTION!
!
Insulation test voltage may not ex-
ceed 500 V.
NOTE!
If many loop measurements are per-
formed with the PROFITEST PRIME in
quick succession, fine-wire fuses in
the PROFITEST REMOTE may blow. This
is due to the increased test current in
order to achieve a higher measuring
accuracy.
➭ Perform the measurement as described
in the operating instructions for the test
instrument:
PROFITEST PRIME: sections 8.6 and 13
➭ Loop impedance is measured using the
Z
LOOP AC/DC measurement variant.
Test
Sequence
Z
L-PE
LED Display (red)
01/3 L1-PE LED1 + LED11
02/3 L2-PE LED2 + LED11
03/3 L3-PE LED3 + LED11
PROFITESTREMOTE Measurements