Precautions for using R32 refrigerant 
The basic installation work procedures are the same as the conventional refrigerant 
(R410A). However, pay attention to the following points: 
CAUTION 
1. 
Transport of equipment containing flammable refrigerants 
Compliance with the transport regulations 
2. 
Marking of equipment using signs 
Compliance with local regulations 
3. 
Disposal of equipment using flammable refrigerants 
Compliance with national regulations 
4. 
Storage of equipment/appliances 
The storage of equipment should be in accordance with the manufacturer's 
instructions. 
5. 
Storage of packed (unsold) equipment 
Storage package protection should be constructed such that mechanical 
damage to the equipment inside the package will not cause a leak of the 
refrigerant charge. 
The maximum number of pieces of equipment permitted to be stored together will 
be determined by local regulations. 
6. 
Information on servicing 
6-1 
Checks to the area 
Prior to beginning work on systems containing flammable refrigerants, safety 
checks are necessary to ensure that the risk of ignition is minimized. For repair 
to the refrigerating system, the following precautions shall be complied with 
prior to conducting work on the system. 
6-2 
Work procedure 
Work shall be undertaken under a controlled procedure to minimize the risk of 
flammable gas or vapor being present while the work is being performed. 
6-3 
General work area 
All maintenance staff and others working in the local area shall be instructed on 
the nature of work being carried out. Work in confined spaces shall be avoided. 
The area around the workspace shall be sectioned off. Ensure that the 
conditions within the area have been made safe by control of flammable 
material. 
6-4 
Checking for presence of refrigerant 
The area shall be checked with an appropriate refrigerant detector prior to and 
during work, to ensure the technician is aware of potentially flammable atmospheres. 
Ensure that the leak detection equipment being used is suitable for use with 
flammable refrigerants, i.e. non-sparking, adequately sealed or intrinsically 
safe. 