Goodwe GW6000-ET handleiding

158 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 13 van 158
13
Smart
meter
GM3000
GM330
GM3000: the CT cannot be replaced. CT
ratio: 120A: 40mA.
GM330: order the CT for GM330 from
GoodWe or other suppliers. CT ratio:
Na: 5A.
nA: CT primary input current, n
ranges from 200 to 5000.
5A: CT Secondary input current.
Smart
dongle
WiFi/LAN Kit-20
LS4G Kit-CN
4G Kit-CN
4G Kit-CN-G20
4G Kit-CN-G21
Ezlink3000
In single inverter system, install the
WiFi/LAN Kit-20.
LS4G Kit-CN, 4G Kit-CN, 4G Kit-CN-
G20 or 4G Kit-CN-G21 is only applicable
to China and used in single inverter
system.
In parallel scenarios, the EzLink 3000
must be connected to the master
inverter. Do not connect any
communication module to the slave
inverters.
The firmware version of EzLink should
be 04 or above.
3.2 Product Overview
3.2.1 Inverter
Inverters control and optimize the power in PV systems through an integrated energy management
system. The power generated in the PV system can be used, stored in the battery, output to the
utility grid, etc.
序号
部件
说明
1
DC switch
Control DC input connection or disconnection.
2
Breather valve
-
3
PV input terminal
Connect the PV module DC input cables.
GW6000-ET-20and GW8000-ET-20: MPPT x 2
GW9900-ET-20, GW10K-ET-20, GW12K-ET-20, GW15K-