02 Safety Precaution
2
User Manual V1.2-2025-01-16
2.1 General Safety
2.2 DC Side
NOTICE
• The information in this document is subject to change due to product updates or other
reasons. This manual cannot replace the product labels or the safety precaution unless
otherwise specied. All descriptions here are for guidance only.
• Before installations, read through the user manual to learn about the product and the
precautions.
• All installations should be performed by trained and knowledgeable technicians who are
familiar with local standards and safety regulations.
• Wear anti-static gloves, cloths, and wrist strips when touching electronic components to
protect the inverter from damage. The manufacturer shall not be liable for any damage
caused by statis electricity.
• Strictly follow the installation, operation, and conguration instructions in this manual. The
manufacturer shall not be liable for equipment damage or personal injury if you do not
follow the instructions. For more warranty details, visit :
• https://en.goodwe.com/warranty.asp.
WARNING
• Ensure that the PV module frames and the PV mounting system are securely grounded.
• Ensure that the DC cables are connected tightly and securely.
• The PV modules used with the inverter must have an IEC61730 class A rating.
• Make sure that the PV strings connected to the same MPPT should contain the same
number of identical PV modules.
• To maximize the power generation of the inverter, please ensure that the Vmp of the PV
modules connected in series is within the MPPT Voltage Range at Nominal Power of the
inverter, as shown in the Technical Parameters.
• Make sure that the voltage dierence between two MPPTs shall be less than 150 V.
• Make sure that the input current of each MPPT does not exceed the Max. Input Current
per MPPT, as shown in the the Technical Parameters.
• When there are multiple PV string inputs, please connect them to as much inverter MPPTs
as possible.
DANGER
• Connect the DC cables using the delivered DC connectors and terminals. The manufacturer
shall not be liable for the equipment damage if other connectors or terminals are used.
• Conrm the following information before connecting the PV string to the inverter.
Otherwise, the inverter may be damaged permanently or even cause re and cause
personal and property losses. Above damage or injuries are not covered by the warranty.
• Make sure that the positive pole of the PV string connects to the PV+ of the inverter. And
the negative pole of the PV string connects to the PV- of the inverter.
• For the models of GW75K-SMT, GW80K-SMT, the open circuit voltage of the PV string
connected to each MPPT shall not exceed 1100V. When the input voltage is between
1000V and 1100V, the inverter enters the waiting mode. When the voltage returns to
180V-1000V, the inverter will resume normal operation.
• For the models of GW50K-SMT-L-G10, the open circuit voltage of the PV string connected
to each MPPT shall not exceed 900V.