09 Maintenance
66
No. Fault Cause Solutions
8
Anti-
islanding
The grid
has been
disconnected.
The grid voltage
is maintained
due to the
presence of
loads. Grid
connection has
been stopped
based on safety
regulations
and protection
requirements.
The inverter will resume grid
reconnection after the grid to return
to normal.
9
LVRT
Undervoltage
Abnormal
grid, and the
abnormal
duration
exceeds the
speci󽗉ed value
of local high
voltage safety
regulation.
1. If occurs occasionally, it may
be caused a short term grid
abnormality. The inverter will
recover automatically after the grid
is normal.
2. If the problem occurs frequently,
check whether the grid voltage is
within the permissible range. If not,
contact the local power company. If
yes, contact the dealer or the after-
sales service.
10
LVRT
Overvoltage
Abnormal
grid, and the
abnormal
duration
exceeds the
speci󽗉ed value
of local high
voltage safety
regulation.