06 Electrical Connection
39
6.5.1 RS485 Communication Networking
NOTICE
• When using the data collector to connect RS485 and inverters, multiple inverters
can be connected to each COM port of the data collector. If the model of Smart
DataLogger is Ezlogger Pro or SEC1000, the maximum number of inverters
connected to per COM port of the Smart DataLogger is 20; if the model of Smart
DataLogger is Ezlogger3000C, the maximum number of inverters connected to per
COM port of the Smart DataLogger is 25. The total length of the connecting cable
should not exceed 1000m.
• If multiple inverters are connected in parallel, the DIP switch of the rst and last
inverter should be turned to ON position (Default), and the inverters in the middle
should be in OFF position.
SDT30NET0005