03 Product Introduction
14
PID Functions
During operation, PV modules experience a potential di󽗈erence between the
output electrodes and the grounded module frame, which over time may
result in reduced module e󽗋ciency—this phenomenon is known as Potential
Induced Degradation (PID).
The PID function of this inverter operates by elevating the voltage di󽗈eren-
tial between the PV panels and their frames to a positive value (termed as
positive-voltage elevation). This e󽗈ectively suppresses the PID e󽗈ect and is
applicable to P-type PV panels as well as N-type PV panels that necessitate
positive - voltage elevation for PID suppression. For N-type PV panels that
demand negative - voltage reduction to suppress the PID e󽗈ect, it is advisable
to deactivate this function. Regarding whether an N-type module falls into the
category that requires positive - voltage elevation for PID suppression, please
consult the module supplier.
3.5 Inverter Operation Mode
Standby
mode
Self-check
mode
Upgrade-
mode
Fault mode
Grid connection
mode