Goodwe GW50K-SDT-C30 handleiding
Handleiding
Je bekijkt pagina 117 van 127

10 Technical Data
113
Operating Temperature
Range (℃)
-30~+60
Derating temperature (℃) 45
Storage Temperature (℃) -30~+70
Relative Humidity 0~100%
Max. Operating Altitude (m) 4000
Cooling Method Smart Fan Cooling
User Interface LED, LCD (Optional), WLAN+APP
Communication RS485, WiFi, LAN or 4G or Bluetooth(Optional)
Weight (kg) 16.6 17.7
Dimension (W×H×D mm) 530×413×221
Noise Emission (dB) <45
Topology Non-isolated
Self-consumption at Night
(W)
<1
Ingress Protection Rating IP66
Anti-corrosion Class C4,C5(Optional)
DC Connector MC4 (4~6 mm² )
AC Connector OT terminal (Max. 16mm²)
Environmental Category 4K4H
Pollution Degree III
Overvoltage Category DC II / AC III
Protective Class I
The Decisive Voltage Class
(DVC)
PV : C
AC : C
Com : A
Active Anti-islanding
Method
*1
AFDPF + AQDPF
Country of Manufacture China
*1: AFDPF: Active Frequency Drift with Positive Feedback, AQDPF: Active Q with Positive
Feedback.
*2: When the input voltage is greater than 1035V, the inverter will enter the standby state, and
the voltage will return to
1030V to enter the normal operation state, considering thatthe detection error may have ±10V
deviation.
*3: When the input voltage is greater than 800V, the inverter will enter the standby state, and
the voltage returns to 785V to enter the normal operation state.