08 System Commissioning
76
User Manual V1.2-2025-04-15
Parameter Description
Reactive Power
Scheduling
• Select one or more DI ports according to the grid company’s require-
ments and RCR xture type, and set the corresponding PF values.
• Support conguration of 16 power factor levels. Congure based on the
actual requirements of the grid company.
• The PF value must be within the ranges [-100, -80] or [80, 100]. Values
in [-100, -80] correspond to a lagging power factor of [-0.99, -0.8], and
values in [80, 100] correspond to a leading power factor of [0.8, 1].
• Do not duplicate the setting of state combinations of DI1–DI4. Other-
wise, the function will not operate properly.
• If the actual DI port wiring connection does not match the web congu-
ration, the operation state will not take eect.