08 System Commissioning
75
User Manual V1.2-2025-04-15
RCR
• The standards of German and other regions require that the inverter must provide signal
controlling port for RCR (Ripple Control Receiver), which can be used for grid scheduling.
• To realize RCR, connect RCR to DI1/DI2/DI3/DI4/REF1 port of the EzLogger for active power
derating, or connect RCR to DI1/DI2/DI3/DI4/REF2 port of the EzLogger for reactive power
scheduling.
Parameter Description
Start Control Enable or disable RCR.
Operation Status
• The operation status of the device. For instance, RCR1(100) means the
current operation state is RCR1, and feed in power accounts for 100% of
the rated power.
• nRCR: operation status does not take eect.
Active Power
Scheduling
• Select one or more DI ports according to the grid company’s require-
ments and RCR xture type, and congure the corresponding percent-
age. Percentage refers to the ratio of the system’s output power to its
rated power.
• Support conguration of 16 percentage levels. Congure based on the
actual requirements of the grid company.
• Do not repeat setting of state combinations of DI1–DI4. Otherwise, the
function will not operate properly.
• If the actual DI port wiring connection does not match the web congu-
ration, the operation state will not take eect.
1
2
3
4
5
6