08 System Commissioning
70
User Manual V1.2-2025-04-15
AC Power Fault Detection
The standards of Japan and other regions require that when there are AC power faults, it is
not allowed to connect the inverter to the utility grid. Connect the external AC power fault detec-
tion device to any DI port of the controller for AC power fault detection.
1
2
3
4
Parameter Description
Access Port
Select the actual port on the EzLogger to which the controller is connect-
ed. Support: DI1, DI2, DI3, DI4.
Initial Contact
State
Select the initial contact state of the port. Support: normally close con-
tact, normally open contact.
Function Switch Enable or Disable AC power fault detection.
Recover to On Grid
Mode
If the the inverter is power o, click Recover to On Grid Mode to restart
and reconnect the inverter to the utility grid .