08 System Commissioning
69
User Manual V1.2-2025-04-15
Remote Shutdown
Parameter Description
Access Port
Select the actual port on the EzLogger which the remote shutdown de-
vice is connected to. Supported: AI1 or AI2.
Function Switch Enable or Disable remote shutdown function.
Recover to On Grid
Mode
If the the inverter is power o, click Recover to On Grid Mode to restart
and reconnect the inverter to the utility grid .
The standards of some countries and regions require that a remote shutdown device should
be connected to the AI1+ or AI2+ port and 12V Output port of the EzLogger to realize re-
mote shutdown function.
The remote shutdown device can detect the voltage and shutdown the inverter through AI1
or AI2 port.
Once the remote shutdown device is disconnected, the voltage of AI1 or AI2 port will
decrease to 0V and the inverter will be shut down. When the remote shutdown device is re-
connected, the voltage of AI1 or AI2 port will increase to 12V. Click Recover to On-grid Mode,
the inverter will restart and connect to the grid.