Furman SmartSequencer CN-1800S handleiding

16 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 9 van 16
8
Delay Indicators
One DELAY LED is featured for each rear outlet delay stage. Each LED
illuminates Green sequentially as each stage completes, indicating power
is available at the corresponding rear panel bank. If the CN-1800S is
operating under safe power conditions and no utility fault conditions exist,
all three Delay LEDs will remain steadily lit when all outlets ON. Once trig-
gered to power-down, each LED goes off in sequence as its correspond-
ing delay bank is deactivated. Note that the DELAY 3 output and the rear
panel DELAY 3 relay contacts are closely associated. When the indicator
DELAY 3 LED is illuminated, the DELAY 3, Common (C) and Normally
Open (NO) terminals are shorted. When the indicator DELAY 3 LED is off,
the DELAY 3, Common (C) and Normally Open (NC) terminals are shorted
DIP 1, DIP 2, and DIP 3: DIP Time Adjustment
There are three DIP switches assigned to control the time delay interval,
DIP switch positions 1, 2, & 3. The time delay, or “dwell time” between
consecutive duplexes is the same whether the CN-1800S is sequenc-
ing ON or OFF. DIP 1 adds 1 minute to the maximum time delay, DIP 2
adds 2 minutes and DIP 3 adds 4 minutes. Note: These time delays are
cumulative. If all three DIP switches are in the UP position, the maximum
allowable time delay will be 7minutes, i.e. 1min+2min+4min=7min. The
factory default setting is DIP 1 ON or UP, and DIP 2 and 3 are OFF or
DOWN. You can set these switches in any position you like to achieve
your preferred time delay.
Delay Adjustment
In order to precisely dial in your preferred sequence dwell time, it is nec-
essary to set the Time Delay Adjustment (DLY ADJ) located next to the DIP
Switch. If this potentiometer is turned to its 100% value (fully clockwise),
then the time delay will be equal to the maximum time delay defined by
DIP switches 1, 2, and 3. If the potentiometer is in the 12:00 o’clock po-
sition (50%), then the time delay will be 50% of the maximum time delay
interval defined by the setting of DIP Switch positions 1,2 & 3. If all three
DIP switches are off, and the potentiometer is turned completely counter-
clockwise, the time delay is miminal. The Delay Adjustment potentiometer
comes factory-set at 50%, the 12 o’clock position.
Example: If the DIP Switches are set to a 6 minute maximum delay
and the potentiometer is set to its 50% setting, then the delay interval
between sequenced banks will be 3 minutes. (DIP 1 OFF or DOWN, DIP 2
and DIP 3 ON or UP) x .50 = 6 minutes x .50 = 3 minutes.
PRIMARY LINK
SECONDARY LINK
ETHERNET
DELAY 1
DELAY 2
DELAY 3
POWER
PROTECTION OK
EXTREME VOLTAGE
UNSWITCHED
START
SEQUENCE
15 AMPS
PUSH TO RESET
ON
OFF
REMOTE
DLY
ADJ
1 2 3 4 5 6 7 8 9
1M
1 2 3 4 5
2M
4M
N.O.
N.C.
12V ON
12V OFF
GND
ON
MOM
MNT
PRI
SEC
EVS AUTO
MANUAL
6 7 8 9
PRIMARY LINK
SECONDARY LINK
ETHERNET
DELAY 1
DELAY 2
DELAY 3
POWER
PROTECTION OK
EXTREME VOLTAGE
UNSWITCHED
START
SEQUENCE
15 AMPS
PUSH TO RESET
ON
OFF
REMOTE
DLY
ADJ
1 2 3 4 5 6 7 8 9
1M
1 2 3 4 5
2M
4M
N.O.
N.C.
12V ON
12V OFF
GND
ON
MOM
MNT
PRI
SEC
EVS AUTO
MANUAL
6 7 8 9
Duplex 1 is powered on
Duplex 2 is powered on
Duplex 3 is powered on
Delay 3 contacts react in time with DELAY 3 Outlets
DELAY INDICATORS
DELAY 1
DELAY 2
DELAY 3
DIP Switch and Delay Adjustment
The DIP Switch is found at the center of the front panel, under the “F”
logo Security Cover. You will need to remove the cover by removing the
two M3 screws to gain access to the DIP switch. The DIP Switch is used
to set various sequencer options. It is also used in combination with the
DLY ADJ pot to set range intervals for the SWITCHED banks. The time DIP
switch settings are ON in the UP position and OFF in the DOWN position.
1 2 3 4 5 6 7 8 9
ON
DLY
ADJ
DLY
ADJ
1M
1 2 3 4 5
2M
4M
N.O.
N.C.
12V ON
12V OFF
GND
ON
MOM
MNT
PRI
SEC
EVS AUTO
MANUAL
6 7 8 9
ON
OFF
Factory-set DIP Settings:
DIP SWITCH DEFAULT SETTING -
Switches are factory pre-set as shown
below. Switches 1, 4, 8, and 9 are up
(ON) position.
NOTE: The DIP switch
ON / OFF settings are
indicated as shown
below throughout
this manual.
1M = 1 Minute Delay
2M = 2 Minute Delay
4M = 4 Minute Delay
NOTE: DIP 1, 2 & 3 can be summed together up to 7 minutes.
N.O. / N.C. sets Forced Off alarm poles
The out of the box factory setting is “normally open”. When sequence is “ON”.
Switched outlets will be ON until a dry contact closure is applied across the
FORCE OFF poles.
12VDC ON/OFF sets +12V pole in
Remote Mode (DIP 7 set to MNT)
Chooses +12V to REM pole functionality. In default OFF mode, a dry closed
contact across +12V to REM triggers sequencer OFF. If ON mode, closed contact
triggers ON.
• 12V OFF = Short Deactivates
• 12V ON = Short Activates
GROUND ON / OFF
Activates REM to GND pole functionality.
• REMOTE TO GROUND = ON
DIP 1
DIP 2
DIP 3
DIP 4
DIP 5
DIP 6