F1500-UPS E Front Panel Installation
The F1500-UPS E is shipped with the front panel unattached to ensure that no damage is caused during shipping. The front panel must be installed before using.
To ensure maximum battery life, it is highly recommended that you al-
low the battery of your F1500-UPS E to charge for at least six to eight
hours prior to initial use. Loss of charge can occur during shipping and
storage and it is best to allow the batteries to fully recharge before
operating the UPS under battery power. To recharge the battery, simply
leave the unit plugged into an AC outlet. The UPS will charge in the ON
as well as the OFF state. If you wish to use the software, connect the
enclosed USB cable to the USB port on the F1500-UPS E and an open
USB port on the computer or server.
DO NOT plug a space heater, vacuum cleaner, paper shredder or other
large electrical device into the F1500-UPS E. The power demands of
these devices will overload and possibly damage the UPS.
Plug the F1500-UPS E into a Schuko grounded receptacle. Make
sure that the branch circuit is protected by a fuse or circuit breaker
and does not service equipment with large electrical demands (e. g.
refrigerator, copier, etc.). Avoid using extension cords. If an extension
cord is used, the cord must be HAR certified for the country in which
the unit is deployed, minimum 1mm
2
, 3-wire grounded, and rated for
10 Amps. Power cord retainer clips are provided to secure the IEC end
of the power cord to the rear of the F1500-UPS E. The clips should be
installed using only the 3mm by 6.6mm screws provided with the UPS.
The F1500-UPS E will automatically charge the battery whenever it is
plugged into an AC outlet. To maintain optimal battery charge, leave the
F1500-UPS E plugged into an AC outlet at all times.
Installation
NOTE: To store your F1500-UPS E for an extended period, cover and
store it with the battery fully charged. Plug the unit in and recharge the
battery every three months to ensure maximum battery life.
COMMUNICATION INTERFACE
BlueBOLT™ Compatible (with BlueBOLT-CV1 interface card, sold sepa-
rately): provides remote access to reboot components, power equipment
on or off, and monitor power quality from anywhere in the world. Contact
Furman for price and availability.
The RS-232 communication card provided with the F1500-UPS E al-
lows connection and communication between the F1500-UPS E and an
automation, media server, or computer system. This allows an installer
to program a number of variables including the Critical Load Battery
Thresholds. See the software documentation for more information.
EXTERNAL BATTERY CONNECTORS
Furman’s BAT1500-EXT external battery pack (sold separately) offers
extended battery runtime when used in conjunction with the Furman
F1500-UPS E. Contact Furman for price and availability.
BANKS
1 2 3 4
POWER MENU
WIRING
FAULT
BANKS
1 2 3 4
POWER MENU
PROTECTION
OK
BANKS
1 2 3 4
POWER MENU
PROTECTION
OK
F1500-UPS E FRONT PANEL INSTALLATION
1. Remove front panel from shipping
inserts.
2. Verify that the battery connectors are
connected, red-to-red, black-to-black (pic).
If not connected, perform steps 2 and 6 in the
BATTERY REPLACEMENT section
3. (Optional) Install the supplied rubber
end-caps to the sides of the front panel.
Push the curved edge of the end-cap into
the mating slots of the front panel.
4. Carefully align the front
panel connector latches with the
slots in the F1500-UPS E.
5. Gradually apply pressure to the
left and right ends of the front panel
until you hear the latches ‘click’
1. Power off and unplug the UPS. Remove the front panel. Remove the rubber end caps and pull up on the latch mechanism.
Once the latch mechanism stops, gradually pull the front panel off of the F1500-UPS E.
2. Remove the screw from the battery connector security plate to release
the battery connector.
3. Disconnect both the red and black connectors.
4. Remove the screws from the battery pack (part number BC-1500) and pull the battery pack out of the unit using the integrated handle.
5. Install the new battery pack into the unit. DO NOT ATTEMPT TO REPLACE THE BATTERIES
IN THE ORIGINAL BATTERY PACK. IMPROPER INSTALLATION CAN RESULT IN FIRE OR
BATTERY LEAKAGE.
6. Reconnect the red and black connectors.
WARNING! ALWAYS CONNECT RED to RED and BLACK to BLACK.
If the cable connectors do not snap together easily as RED to RED
and BLACK to BLACK, NEVER attempt to force them together or connect
RED to BLACK which will cause electrical sparking, shock, fire or
explosion! Call Customer Service for help.
8. Reinstall the front panel per the Front Panel Installation instructions.
MB1500/F1500-UPS BATTERY REPLACEMENT
The F1500-UPS E is shipped with the front panel unattached to ensure that no damage is caused during shipping. Before the F1500-UPS E can be used, the front panel must be installed.
7. Reinstall the battery connector
security plate.