6.7.3 External input terminal
• Setting to low noise mode, outdoor unit operation peak control setting, emergency/batch
stop and electricity meter pulse are possible from the outside.
Exceptforwattmeterpulsereception(CN135)amongexternalinputterminals,onlythe
primary unit is effective.
Wiring method and specifications
* Atwistedpaircable(0.33mm²(22AWG))shouldbeused.Maximumlengthofcableis
150 m.
* Useanexternalinputandoutputcablewithappropriateexternaldimension,depending
on the number of cables to be installed
* For each input, pin No. 1 is of positive polarity and pin No. 2 is of ground level.
CN131 CN133 CN134
CN135
Connected unit Connected unit Connected unit Connected unit
(Brown) (White) (Purple) (Orange)
P.C.B
Input 1
Input 3
Input 4
Input 5
Operation behavior
Each input terminal works as follows.
Connector
Input
signal
Status
Outdoor unit
Primary
Subor-
dinate
Input 1
CN131 (Broun)
OFF Normal operation
ON Low noise mode operation
Input 3
CN133 (White)
OFF Normal operation
ON
Outdoor unit operation peak
control
Input 4
CN134 (Purple)
OFF Normal operation
ON
Batch stop or Emergency stop
operation (*1)(*2)
Input 5
CN135 (Orange) (*3)
No pulse
No information from electricity
meter
Pulse
Power usage information from
electricity meter
Subordinate unit can connect only input 5 (CN135).
The operations of each input terminal and the selection of function are set with the push
button on the PC board of outdoor unit. About the setting, please refer to “7. 4. Push but-
ton setting”.
NOTES:
*1: Batch stop or Emergency stop pattern can be selected by outdoor unit PC board
push button. (Refer to “7. FIELD SETTING”.)
*2: The emergency stop function mounted in this model does not guarantee the regula-
tions of each country. For this reason, sufficient checking is necessary regarding
use.
Especially, since the fact that the equipment may not be emergency-stopped in the
caseofbreakingofthewiringtotheexternalinputterminalsandcommunication
line,communicationerrorduetonoise,VRFexternalinputcircuittrouble,etc.must
be considered, the provision of double measures that add direct interruption of the
power supply by switch, etc. is recommended as a precaution.
*3: Pulse input to CN135 must be width 50 ms or more, and must be interval 50 ms or
more.
6.7.4 External output terminal (primary unit only)
• You can detect the operation condition of outdoor unit and the abnormal situation of both
indoor and outdoor unit.
Theexternaloutputterminalisonlyvalidforprimaryunit.
Wiring method and specifications
Error status
This output indicates the outdoor unit
and connected indoor unit's “Normal” or
“Error” status.
Operation status
This output indicates the outdoor unit's
“Operation” status.
Connector
Output
voltage
Status
Output 1
CN136
(Black)
0 V Normal
DC 12-24 V
(*1)
Error
Output 2
CN137
(Blue)
0 V Stop
DC 12-24 V
(*1)
Operation
P.C.B.
CN136 (Black) or
CN137 (Blue)
DC power supply
(External)12-24V
Connected load (Operation Indica-
tor or Error Indicator)
Connected unit
*1: Provide a DC 12 to 24 V power supply.
Select a power supply capacity with an ample surplus for the connected load.
*2: The allowable current is 30 mA or less.
Provide a load resistance such that the current becomes 30 mA or less.
*3: Polarityis[+]forpin1and[-]forpin2.Connectcorrectly.
Donotimpressavoltageexceeding24Vacrosspins1-2.
Atwistedpaircable(0.33mm²(22AWG))shouldbeused.
Maximumlengthofcableis150m.
Useanexternalinputandoutputcablewithappropriateexternaldimension,depending
on the number of cables to be installed.
7. FIELD SETTING
CAUTION
Discharge the static electricity from your body before setting up the DIP switches.
Never touch the terminals or the patterns on the parts that are mounted on the PC
board.
7.1. Field setting switches
Remove the service panel of the outdoor unit and the cover of the electrical component
boxtoaccessthePCboardoftheoutdoorunit.
PC board switches for various settings and LED displays are shown in the figure.
SW109SW108SW107
D306
LED101 LED102
D305 D304 D303
SW101
SW105
SW102 SW103 SW104
SW111
LED104LED105
D301
D300
MODE/
EXIT
SELECT
SET1
POWER
ERROR
ENTER
×10 ×1
REF AD
SET2 SET3 SET4
SET5
SW106
7-segment display
LED lamp
Push button
Rotary switch
Main PC board
DIP switch
DIP switch
7.2. DIP switch setting
7.2.1 List of settings
SET2, SET3 and SET5 must be
set for the DIP switch. Set SET4
as necessary.
Configure the settings before
turning on the power. Settings for
SET1 DIP switches are factory de-
fault ones. Do not change them.
*1: Pressure sensor kit (indoor
unit optional parts)
*2: For detailed instructions, refer
to the service manual.
DIP Switch Function
SET 1 1-4 Prohibited
SET 2
1-3 Prohibited
4
When use the UTY-SPWX (*1),
turn this switch on.
SET 3
1
Outdoor unit address setting
2
3
Setting for number of subordinate
units
4
SET 4
1 Prohibited
2
When activate emergency opera-
tion, turn this switch on. (*2)
3-4 Prohibited
SET 5
1 Terminal resistor setting (H1, H2)
2-3 Prohibited
4
Terminal resistor setting (X1, X2,
Z1, Z2)
7.2.2 Settings to be congured locally
(1) Outdoor unit address setting
When 2 or 3 outdoor
units are installed to 1
refrigerant system, set the
address for each outdoor
unit.
Set the address for all
outdoor units.
SET3 Outdoor
unit ad-
dress
Remarks
1 2
OFF OFF 0
Primary unit
(Factory setting)
OFF ON 1 Subordinate unit 1
ON OFF 2 Subordinate unit 2
ON ON 3 Subordinate unit 3
9378945746-02_IM_En_240404_2.indd 169378945746-02_IM_En_240404_2.indd 16 2024/04/04 16:26:082024/04/04 16:26:08