Problem Possible Cause Possible Solution
Unit short cycles
Defective thermistor Replace thermistor or electronic control board
Unit oversized See sizing chart. Correct as needed.
Chassis seal gasket not sealing or ab-
sent causing unit to short cycle
Check gasket. Reposition or replace as needed
Restricted coil or dirty filter
Clean & advise customer of periodic cleaning & maintenance needs of entire
unit
Prolonged off cycles
Defective indoor ambient thermistor or
electronic control board
Check alarms. Replace thermistor or electronic control board
Outside water leaks
Evaporator drain pan cracked or ob-
structed
Repair, clean or replace as required
Obstructed condenser coil Use pressure wash or biodegradable cleaning agent to clean
Fan blade/ slinger ring improperly
positioned
Adjust fan blade to 1/2” of condenser coil fin pack
Room temperature uneven
(Heating cycle)
Bad indoor ambient thermistor Check diagnostic codes. Check Thermistors. Replace as needed.
Fan speed too low Set at higher fan speed.
Does not heat adequately
Exhaust or fresh air door open Check if operating properly. Instruct customer on proper use of control
Dirty filter Clean (See Routine Maintenance)
Unit undersized
Check heat rise across coil. If unit operates efficiently, check if insulation can
be added to attic or walls. If insulation is adequate, recommend additional
unit or larger one
Heater hi-limit control cycling on & off Check for adequate fan air across heater. Check for open hi-limit control.
Shorted or open supplementary heater Do ohmmeter check.
Incorrect wiring Check applicable wiring diagram
Unit cools when heat is called
for
Incorrect wiring Refer to applicable wiring diagram
Defective solenoid coil Check for continuity of coil
Reversing valve fails to shift
Block condenser coil & switch unit to cooling. Allow pressure to build up in
system, then switch to heating. If valve fails to shift, replace valve.
Cooling adequate, but heating
insufficient.
Reversing valve failing to shift com-
pletely; bypassing hot gas
De-energize solenoid coil, raise head pressure, energize solenoid to break
loose. If valve fails to make complete shift, replace valve.
TROUBLESHOOTING
Troubleshooting Tips
Figure 606