TROUBLESHOOTING
Troubleshooting Tips
Problem Possible Cause Possible Solution
Compressor runs continually &
does not cycle off
Excessive heat load
Unit undersized. Test cooling performance & replace with larger unit if
needed. See sizing chart.
Restriction in line Check for partially iced coil & check temperature split across coil
Thermistor shorted Replace thermistor or electronic control board
Electronic control
board does not turn unit off
Compressor relay contacts stuck Replace electronic control board
Incorrect wiring Refer to appropriate wiring diagrams
Unit undersized for area to be cooled Refer to industry standard sizing chart
Defective thermistor Replace thermistor or electronic control board
Compressor runs for short
periods only.
Incorrect wiring Refer to appropriate wiring diagram
Shorted or incorrect capacitor Test capacitor and replace if needed.
Restricted or low air flow through con-
denser coil or evaporator coil
Check for proper fan speed or blocked coils. Correct as needed.
Compressor running abnormally hot
Check for kinked discharge line or restricted condenser. Refrigerant over-
charge. Check amperage, connections.
Unit does not turn on
No power
Check power supply. Check LCDI plug. Check wire connections. Check if
panel is locked.
Incorrect wiring Refer to appropriate wiring diagram.
Defective thermistor Replace thermistor or electronic control board.
Noisy operation
Poorly installed Refer to Installation Manual for proper installation.
Fan blade striking chassis Reposition - adjust motor mount.
Compressor vibrating
Check that compressor grommets have not deteriorated. Check that com-
pressor mounting parts are not missing.
Improperly mounted or loose cabinet
parts refrigerant tubes
Check assembly & parts for looseness, rubbing & rattling pipes, etc.
Water Leaks into Room
Evaporator drain pan overflowing Clean obstructed drain trough.
Condensation forming underneath base
pan
Evaporator drain pan broken or cracked. Reseal or replace. No chassis
gasket installed. Install chassis gasket.
Poor installation resulting in rain enter-
ing the room
Check installation instructions. Reseal as required.
Condensation on discharge grille
louvers
Dirty evaporator coil. Clean coils (See Routine Maintenance) Environmental
phenomena: point supply louvers upward. Put on high fan.
Chassis gasket not installed Install gasket, per Installation manual.
Downward slope of unit is too steep
inward
Refer to installation manual for proper installation.
Water “spitting” into room
Sublimation:
When unconditioned saturated, outside
air mixes with conditioned air, conden-
sation forms on the cooler surfaces
Ensure that foam gaskets are installed in between window panes & in
between the unit & the sleeve. Also, ensure that fresh air/exhaust vents (on
applicable models) are in the closed position & are in tact.
Downward pitch of installation is too
steep towards back of unit
Follow installation instructions to ensure that downward pitch of installed
unit is no less than 1/4” & no more than 3/8”
Restricted coil or dirty filter
Clean & advise customer of periodic cleaning & maintenance needs of entire
unit
Excessive moisture
Insufficient air circulation thru area to be
air conditioned
Adjust louvers for best possible air circulation
Inadequate vapor barrier in building
structure; particularly floors.
Advise customer
Figure 606