IPL EXP I/O Series • Software-based Configuration and Control 35
Device Control Connections and Configuration
Verify that ports are wired correctly and that ground (earthing) wires are connected to the proper pins on the
control processor and, if applicable, on the controlled device.
Ensure that each IR emitter head is placed adjacent to or directly over the IR pickup window on the controlled
device.
Verify that the appropriate drivers were used while creating the configuration file and that the correct
commands and signal types (IR, RS-232, Ethernet) are associated with the appropriate ports on the control
processor and on the other devices.
For digital input and output connections, verify whether the application requires the +5 VDC pull-up
resistor within the IPL EXP for TTL circuits, and use the software to check whether it is selected within the
configuration.
Verify that input current at any digital input or output port does not exceed 250 mA.
If you are still experiencing problems, call the Extron Sales & Technical Support Hotline or the Extron S3
Control Systems Support Hotline (1.800.633.9877).
Rev. B: Deleted subsection on
troubleshooting eBUS devices.