43 Automatic settings
Control System KNX WS1000 Style • Version: 28.05.2018 • Technical changes and errors excepted.
The conditions for the triggering of the movement limitation (outdoor temperature, pe-
riod) are defined in the "General Settings" menu.
System > Automatic Setttings > General Settings > Movement Limitation
3.3. Set movement limitations (windows)
Confirm your setting by pressing OK.
Press the button to set the movement position when movement limitation is active.
The button will only be activated once the movement limitation has been activated.
Input the maximum movement position in % using the arrow buttons (0% = closed,
100% = fully open). Default: 50%.
The window can be reopened fully by hand.
Confirm your setting using the OK button.
Confirm your setting by pressing OK.
Press the button to set the outdoor temperature block. The effect of the block is that the
window remains in the current position. The outdoor temperature block can, for exam-
ple, be used if the window should not be used for ventilation in winter (cold protection
for plants).
The outdoor temperature block only applies for automatic operation; no ventilation
then takes place. When the rain or wind alarm is triggered, the window will be closed
despite the outdoor temperature block (the alarm has priority over temperature block).
Manual operation continues to remain possible, even when the window is blocked be-
cause of low outdoor temperatures.
Set value:
Use the arrow buttons to change the value according to your wish. Default
setting: 5.0°C
The outdoor temperature-block becomes active as soon as the temperature sinks un-
der the pre- set value. The block is however only deactivated again when the temper-
ature rises over the pre-set value by more than 2.0°C (hysteresis).
Disable block:
If the window should be controlled independently of the outdoor tem-
perature, press the button Off.
Confirm your setting with the OK button.
Press the button to set the closure time. Closure periods prevent the windows, for ex-
ample, from opening and closing at night, and thus causing noise. Note that no night-
time re-cooling is possible during the set closure periods.