39 Automatic settings
Control System KNX WS1000 Style • Version: 28.05.2018 • Technical changes and errors excepted.
3.1.6. Automatic window settings
For connected windows, sliding roofs, step windows or window groups, the following
automatic settings can be changed:
Indoor sensor to be used for the window
Indoor temperature
Air humidity
Supply air temperature
Night-time re-cooling (together with indoor temperature and movement
position for night-time re-cooling)
Movement position (only for sliding windows)
Number of steps (only for step windows)
Timed ventilation
Outdoor temperature
Timed closure
Frost alarm
Wind alarm
Rain alarm
Gap ventilation
Gap position
Enable/Disable automatic reset
Alarm Functions
Alarm functions are used for windows in manual and in automatic mode.
During frost, wind or rain alarm all windows are closed and cannot be manually
opened. Gap ventilation during a rain alarm is an exception; it only restricts the win-
dow's range of motion in automatic mode.
As soon as a connected air conditioner is activated, all windows are closed. They
are then in automatic mode but can be immediately operated again. The delay time for
the ventilation block engaged by an air conditioner can be adjusted.
System > Automatic Settings > General Settings > Ventilation Block
3.3. Adjust ventilation block
Ventilation settings
The settings are only executed if a window is in automatic mode and none of the alarm
functions named above is active.
Highest priority is assigned to time closure, followed by the outdoor temperature-
block (keep closed), timed ventilation (open), the incoming air temperature-block
(keep closed) and night-time re-cooling (open).
This means that e.g. timed ventilation or night-time re-cooling will only occur, when
the outdoor temperature lies over the pre-set value for the outdoor temperature block.
The automatic ventilation according to temperature or relative humidity is only
performed if no block is active.