44 Parameter setting
Sensor KNX VOC/TH-UP Touch • Version: 30.11.2021 • Technical changes and errors excepted.
8.10. Absolute humidity
The absolute air humidity value is detected by the KNX VOC/TH-UP Touch and can
be output to the bus.
8.11. Comfort field
The Sensor KNX VOC/TH-UP Touch can send a message to the bus if the limits of
the comfort field are exceeded. In this way, it is for example possible to monitor com-
pliance with DIN 1946 (standard values) or even to define your own comfort field.
Define the comfort field by specifying the minimum and maximum values for temper-
ature and humidity. The specified standard values comply with DIN 1946
Switching output sends on change and
periodically
Send switching output status
Switching output sends on change to 1
and periodically
if switching output = 1 send 1
Switching output sends on change to 0
and periodically
if switching output = 0 send 0
Use absolute humidity No • Yes
Sending pattern • never
• periodically
• on change
• on change and periodically
At and above change of
(if sent on change)
0,1 g • 0,2 g • 0,5 g • 1,0 g • 2,0 g • 5,0 g
Send cycle
(if sent periodically)
5 s • 10 s • 30 s… • 2 h
Use comfort field No • Yes
Sending pattern • never
• periodically
• on change
• on change and periodically
Send cycle (if sent periodically) 5 s • 10 s • 30 s… • 2 h
Maximum temperature in °C
(Standard 26°C)
25 ... 40; 26
Minimum temperature in °C
(Standard 20°C)
10 ... 21; 20
Maximum relative humidity in %
(Standard 65%)
52 ... 90; 65