Elsner KNX VOC/TH-UP Touch handleiding
Handleiding
Je bekijkt pagina 20 van 68

18 Transfer protocol
Sensor KNX VOC/TH-UP Touch • Version: 30.11.2021 • Technical changes and errors excepted.
106 VOC threshold value 1: Switching
delay from 0 to 1
Input -WC- [7.5] DPT_TimePeri-
odSec
2 Bytes
107 VOC threshold value 1: Switching
delay from 1 to 0
Input -WC- [7.5] DPT_TimePeri-
odSec
2 Bytes
108 VOC threshold value 1: Switching
output
Output R-CT [1.1] DPT_Switch 1 Bit
109 VOC threshold value 1: Switch out-
put block
Input -WC- [1.2] DPT_Bool 1 Bit
110 VOC threshold value 2: Absolute
value
Input /
Output
RWC
T
[9.8] DPT_Value_Air-
Quality
2 Bytes
111 VOC threshold value 2: (1:+ | 0:-) Input -WC- [1.2] DPT_Bool 1 Bit
112 VOC threshold value 2: Switching
delay from 0 to 1
Input -WC- [7.5] DPT_TimePeri-
odSec
2 Bytes
113 VOC threshold value 2: Switching
delay from 1 to 0
Input -WC- [7.5] DPT_TimePeri-
odSec
2 Bytes
114 VOC threshold value 2: Switching
output
Output R-CT [1.1] DPT_Switch 1 Bit
115 VOC threshold value 2: Switch out-
put block
Input -WC- [1.2] DPT_Bool 1 Bit
116 VOC threshold value 3: Absolute
value
Input /
Output
RWC
T
[9.8] DPT_Value_Air-
Quality
2 Bytes
117 VOC threshold value 3: (1:+ | 0:-) Input -WC- [1.2] DPT_Bool 1 Bit
118 VOC threshold value 3: Switching
delay from 0 to 1
Input -WC- [7.5] DPT_TimePeri-
odSec
2 Bytes
119 VOC threshold value 3: Switching
delay from 1 to 0
Input -WC- [7.5] DPT_TimePeri-
odSec
2 Bytes
120 VOC threshold value 3: Switching
output
Output R-CT [1.1] DPT_Switch 1 Bit
121 VOC threshold value 3: Switch out-
put block
Input -WC- [1.2] DPT_Bool 1 Bit
122 VOC threshold value 4: Absolute
value
Input /
Output
RWC
T
[9.8] DPT_Value_Air-
Quality
2 Bytes
123 VOC threshold value 4: (1:+ | 0:-) Input -WC- [1.2] DPT_Bool 1 Bit
124 VOC threshold value 4: Switching
delay from 0 to 1
Input -WC- [7.5] DPT_TimePeri-
odSec
2 Bytes
125 VOC threshold value 4: Switching
delay from 1 to 0
Input -WC- [7.5] DPT_TimePeri-
odSec
2 Bytes
126 VOC threshold value 4: Switching
output
Output R-CT [1.1] DPT_Switch 1 Bit
127 VOC threshold value 4: Switch out-
put block
Input -WC- [1.2] DPT_Bool 1 Bit
128 VOC controller: Block object Input -WC- [1.2] DPT_Bool 1 Bit
129 VOC controller: Setpoint Input /
Output
RWC
T
[9.8] DPT_Value_Air-
Quality
2 Bytes
No Text Function Flags DPT type Size