72 Adjustment
Room Controller KNX Touch One Style • Status: 30.07.2020 • Errors excepted. Subject to technical changes.
The frost alarm is triggered in the following situations:
• The external temperature is below the set frost alarm temperature and it is
beginning to rain/snow.
• The external temperature drops below the set frost alarm temperature while it
is raining/snowing.
• It has rained/snowed. The external temperature falls below the set frost alarm
temperature within the set standby period after the end of the precipitation.
The frost alarm ends in the following situations:
• The external temperature remains above the set dew point temperature for the
period of time.
Triggering the frost alarm:
First, determine when the frost alarm is triggered. Use the
arrow buttons to adjust the outdoor temperature that must be undercut to trigger the
frost alarm (e. g. 2.0 °C).
Then, set the number of hours during or after a precipitation which the external tem-
perature must undercut this in order to trigger a frost alarm (e. g. 5 hours).
Ending a frost alarm:
Use the arrow buttons to determine the outdoor temperature that
must be exceeded to end the frost alarm (e. g. 5.0 °C). Then set how many hours the
external temperature must be exceeded in order to end the frost alarm (e. g. 5 hrs).
A drive or curtain can be damaged if an external shade which
has frozen stiff is retracted!
Following a manual intervention, the affected drive or light remains in manual mode,
and automatic operations are switched off. Once the general Automatic Function time
point is reached, drives and light applications are once again set to Automatic. Alter-
natively, the automatic function can be set to reactivate following a manual interven-
tion. The period for this can be set.
The Automatic Reset prevents drives from being manually operated and then stay in
an unfavourable position (leaving windows accidentally open, or blinds retracted de-
spite the sunlight).
The general Automatic Reset and reset following a manual intervention can be sepa-
rately activated and de-activated in the Automatic functions menu for each drive group
and each unit.
General Automatic Reset:
Set the time point by selecting the hour and accordingly the minute fields and setting
the time using the arrow buttons. Default setting: 3:00 AM.
Automatic reset following a manual intervention:
Use the arrow keys to set the time interval after which Automatic functions should be
once again activated.Default setting: 60 minutes.