38 Parameter setting
Sensor KNX TH-UP Touch • Version: 05.09.2022 • Technical changes and errors excepted.
Determine the deviation from the setpoint value at which the maximum variable value
is reached, i.e. the point at which maximum output is used.
The reset time shows how quickly the controller responds to deviations from the set-
point value. In case of a short reset time, the control responds with a fast increase of
the control variable. In case of a long reset time, the control responds somewhat less
urgently and needs longer until the necessary control variable for the setpoint value
deviation is reached.
You should set the time appropriate for the humidification/dehumidification system at
this point (note manufacturer instructions).
Now specify, what should be sent when the control is blocked.
On release, the control variable follows the rule again.
6.9. Dewpoint measurement
The Sensor KNX TH-UP Touch calculates the dewpoint temperature and can output
the value to the bus.
Activate the monitoring of the coolant temperature if required. The menus for setting
the monitoring are displayed.
6.9.1. Cooling medium temp. monitoring
A threshold value can be set for the temperature of the coolant, which is based on the
current dewpoint temperature (offset/deviation). The switching output of the coolant
temperature monitoring system can provide a warning prior to any build-up of conden-
sation in the system, and/or activate appropriate countermeasures.
Maximum control variable is reached
at target/actual difference of %
1...50; 5
Reset time in minutes 1...255; 3
When blocked, the control variable shall • not be sent
• send a specific value
Value in %
(if a value is sent)
0...100
Use dewpoint temperature No • Yes
Sending pattern never
periodically
on change
on change and periodically
At and above change of
(if sent on change)
0,1°C • 0,2°C • 0,5°C • 1,0°C • 2,0°C • 5,0°C
Send cycle
(if sent periodically)
5 s • 10 s • 30 s • 1 min • … • 2 h
Use monitoring of the coolant temperature NoYes