36 Parameter setting
Sensor KNX TH-UP Touch • Version: 05.09.2022 • Technical changes and errors excepted.
Configure a block for the humidity control using the blocking object.
Specify when the current control variables are to be sent to the bus. Periodic sending
is safer, in case a message does not reach a recipient. You may also set up periodic
monitoring using an actuator with this setting.
The status object shows the current status of the output variable (0 = OFF,
>0 = ON) and can for example be used for visualisation.
Controller setpoint
Set, in which cases setpoint values received via object are to be retained. Please note
that the setting "After power supply restoration and programming" should not be used
for the initial start-up, as the factory settings are always used until the first communi-
cation (setting via objects is ignored).
During initial commissioning, a setpoint value must be defined which is valid until
the first communication of a new setpoint value. For units which have already been tak-
en into service, the last communicated setpoint value can be used. Basically, an air hu-
midity range is specified in which the setpoint value can be changed (object value
limit).
Enter, how the setpoint value will be received from the bus. Basically, a new value can
be received, or simply a command to increase or decrease.
Type of control • One-level dehumidification
• Two-level dehumidification
• Humidification and dehumidification
Behaviour of the blocking object with value • 1 = block control | 0 = release control
• 0 = block control | 1 = release control
Blocking object value
before first communication
0 • 1
Send control variable • on change
• on change and periodically
from change (in % absolute) 1 ... 20, 2
Send cycle
(is only sent if "periodically" is selected)
5 s • ... • 5 min • … • 2 h
Send status object(s) • on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
Send cycle
(is only sent if "periodically" is selected)
5 s • ... • 5 min • … • 2 h