10 Transfer protocol
Sensor KNX TH-UP Touch • Version: 05.09.2022 • Technical changes and errors excepted.
5. Transfer protocol
Units:
Temperatures in degrees Celsius
Air humidity in %
Absolute air humidity in g/kg and/or g/m
3
Variables in %
5.1. List of all communications objects
Abbreviation flags:
C Communication
R Read
WWrite
T Transfer
UUpdate
No Name Function Flags Data Point Type Size
0 Software version readable R-CT [217.1]
DPT_Version
2 Bytes
1 Temperature/humidity malfunction
sensor
Output R-CT [1.1]
DPT_Switch
1 Bit
3 Outside temperature reading Input -WC- [9.1]
DPT_Value_Temp
2 Bytes
4 Inside temperature reading Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
5 Overall temperature reading Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
6 Min./max. temperature value
request
Input -WC- [1.17]
DPT_Trigger
1 Bit
7 Minimum temperature reading Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
8 Maximum temperature reading Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
9 Reset min./max. temperature value Input -WC- [1.17]
DPT_Trigger
1 Bit
10 Temp. threshold value 1: Absolute
value
Input/
Output
RWCT [9.1]
DPT_Value_Temp
2 Bytes
11 Temp. threshold value 1: (1:+ | 0:-) Input -WC- [1.2]
DPT_Bool
1 Bit
12 Temp. threshold value 1:
Switching delay from 0 to 1
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
13 Temp. threshold value 1:
Switching delay from 1 to 0
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
14 Temp. threshold value 1: Switching
output
Output R-CT [1.1]
DPT_Switch
1 Bit