13 Transfer protocol
Sensor KNX AQS/TH-UP Touch • Version: 02.08.2022 • Technical changes and errors excepted.
58 TR_1_Belimo_Control variable Output R-CT [5.1]
DPT_Scaling
1 Byte
59 Outside humidity reading Input -WC- [9.7]
DPT_Value_Humidity
2 Bytes
60 Inside humidity reading Output R-CT [9.7]
DPT_Value_Humidity
2 Bytes
61 Overall humidity reading Output R-CT [9.7]
DPT_Value_Humidity
2 Bytes
62 Min./max. humidity value request Input -WC- [1.17]
DPT_Trigger
1 Bit
63 Minimum humidity reading Output R-CT [9.7]
DPT_Value_Humidity
2 Bytes
64 Maximum humidity reading Output R-CT [9.7]
DPT_Value_Humidity
2 Bytes
65 Reset min./max. humidity value Input -WC- [1.17]
DPT_Trigger
1 Bit
66 Humidity threshold value 1: Abso-
lute value
Input/
Output
RWC
T
[9.7]
DPT_Value_Humidity
2 Bytes
67 Humidity threshold value 1: (1:+ |
0:-)
Input -WC- [1.2]
DPT_Bool
1 Bit
68 Humidity threshold value 1: Switch-
ing delay from 0 to 1
Input -WC- [[9.010]
DPT_Value_Time
2 Bytes
69 Humidity threshold value 1: Switch-
ing delay from 1 to 0
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
70 Humidity threshold value 1: Switch-
ing output
Output R-CT [1.1]
DPT_Switch
1 Bit
71 Humidity threshold value 1: Switch-
ing output block
Input -WC- [1.2]
DPT_Bool
1 Bit
72 Humidity threshold value 2: Abso-
lute value
Input/
Output
RWC
T
[9.7]
DPT_Value_Humidity
2 Bytes
73 Humidity threshold value 2: (1:+ |
0:-)
Input -WC- [1.2]
DPT_Bool
1 Bit
74 Humidity threshold value 2: Switch-
ing delay from 0 to 1
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
75 Humidity threshold value 2: Switch-
ing delay from 1 to 0
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
76 Humidity threshold value 2: Switch-
ing output
Output R-CT [1.1]
DPT_Switch
1 Bit
77 Humidity threshold value 2: Switch-
ing output block
Input -WC- [1.2]
DPT_Bool
1 Bit
78 Humidity controller: Blocking object Input -WC- [1.2]
DPT_Bool
1 Bit
79 Humidity controller: Target value Input/
Output
RWC
T
[9.7]
DPT_Value_Humidity
2 Bytes