12 Transfer protocol
Sensor KNX AQS/TH-UP Touch • Version: 02.08.2022 • Technical changes and errors excepted.
36 TR_1_ Target value, comfort heat-
ing (1:+ | 0:-)
Input -WC- [1.1]
DPT_Switch
1 Bit
37 TR_1_ Target value, comfort cool-
ing
Input/
Output
RWC
T
[9.1]
DPT_Value_Temp
2 Bytes
38 TR_1_ Target value, comfort cool-
ing (1:+ | 0:-)
Input -WC- [1.1]
DPT_Switch
1 Bit
39 TR_1_ Target value_Basic offset
16 Bit
Input/
Output
RWC
T
[9.1]
DPT_Value_Temp
2 Bytes
40 TR_1_ Target value, Standby heat-
ing
Input/
Output
RWC
T
[9.1]
DPT_Value_Temp
2 Bytes
41 TR_1_ Target value, Standby heat-
ing (1:+ | 0:-)
Input -WC- [1.1]
DPT_Switch
1 Bit
42 TR_1_ Target value, Standby cool-
ing
Input/
Output
RWC
T
[9.1]
DPT_Value_Temp
2 Bytes
43 TR_1_ Target value, Standby cool-
ing (1:+ | 0:-)
Input -WC- [1.1]
DPT_Switch
1 Bit
44 TR_1_ Target value, Eco heating Input/
Output
RWC
T
[9.1]
DPT_Value_Temp
2 Bytes
45 TR_1_ Target value, Eco heating
(1:+ | 0:-)
Input -WC- [1.1]
DPT_Switch
1 Bit
46 TR_1_ Target value, Eco cooling Input/
Output
RWC
T
[9.1]
DPT_Value_Temp
2 Bytes
47 TR_1_ Target value, Eco cooling
(1:+ | 0:-)
Input -WC- [1.1]
DPT_Switch
1 Bit
48 TR_1_ Control variable heating
(stage 1)
Output R-CT [5.1]
DPT_Scaling
1 Byte
49 TR_1_ Control variable heating
stage 2
Output R-CT [5.1]
DPT_Scaling
1 Byte
50 TR_1_ Control variable cooling
(stage 1)
Output R-CT [5.1]
DPT_Scaling
1 Byte
51 TR_1_ Control variable cooling
stage 2
Output R-CT [5.1]
DPT_Scaling
1 Byte
52 TR_1_ Status heating 1 (1=ON |
0=OFF)
Output R-CT [1.1]
DPT_Switch
1 Bit
53 TR_1_ Status heating 2 (1=ON |
0=OFF)
Output R-CT [1.1]
DPT_Switch
1 Bit
54 TR_1_ Cooling status 1 (1=ON |
0=OFF)
Output R-CT [1.1]
DPT_Switch
1 Bit
55 TR_1_ Cooling status 2 (1=ON |
0=OFF)
Output R-CT [1.1]
DPT_Switch
1 Bit
56 TR_1_ Comfort Delay Status Input/
Output
RWC
T
[1.1]
DPT_Switch
1 Bit
57 TR_1_Comfort extension time (in
sec)
Input/
Output
RWC
T
[7.5]
DPT_TimePeriodSec
2 Bytes
No Name Function Flags Data Point Type Size