Use and maintenance manual, model “LIBERA 8 V/C - LIBERA 11 V/C”
ENGLISH
9
should be taken (e.g., installing a load distribution
plate). It is recommended to consult a professional
on the subject.
• The installation room must have a minimum
volume of 50 m
3
• Minimum safety distances for re prevention
must be taken into consideration when installing
the appliance in the room. In the presence of
combustible materials and/or heat-sensitive
materials (furniture, curtains, sofas, wooden walls
and surfaces, building insulation, etc.) adjacent
to the generator, minimum free space must be
observed as per values shown in the relevant
table of the "Safety distances” chapter.
• The use of a protective platform made of suitable
material (steel, glass...) is required. Such platform
must also protects the front part from any falling
combustion materials during loading/cleaning
operations;
• The installation of the appliance must take
into consideration any presence of other heat
generators or suction systems (e.g., hoods,
extractor fans, etc.) for the following purposes:
• summation of the powers, for re-prevention
purposes;
• possible coexistence, e.g., with non-airtight
gas- and/or diesel-fuelled appliances (see
technical standard UNI10683). Remember that
it is forbidden to install non-airtight biomass
appliances in rooms connected with other
premises where there is a type A or type B gas or
diesel generator;
• suitability assessment of the direct and/or
indirect room ventilation system to serve the
suction systems and appliances installed;
• The installer must analyse the technical
specications of the appliance to verify its
compatibility with the energy requirements of
the room(s) served and the coexistence with any
other appliances.
3.2 VENTILATION - AMBIENT AIR INTAKE
• The installation room of non-hermetic appliances
must be sufciently ventilated with special
openings, with particular attention to their position,
which has to ensure air to recirculate. Remember
that non-hermetic appliances feed the re by
consuming the oxygen present in the installation
room.
• Ventilation is considered sufcient when the room
is equipped with air intakes according to the table:
APPLIANCE
CATEGORY
REFERENCE
STANDARD
% NET CROSS-
SECTION
COMPARED TO
STOVE SMOKE
OUTLET CROSS-
SECTION
VENT. DUCT
OPENING MIN.
NET VALUE
Fireplaces UNI EN 16510-2-2:2022 50% 200 cm
2
Stoves UNI EN 16510-2-1:2022 50% 100 cm
2
Cookers UNI EN 16510-2-3:2022 50% 100 cm
2
Pellet stoves UNI EN 16510-2-6:2022 - 80 cm
2
APPLIANCE
CATEGORY
REFERENCE
STANDARD
% NET CROSS-
SECTION
COMPARED TO
STOVE SMOKE
OUTLET CROSS-
SECTION
VENT. DUCT
OPENING MIN.
NET VALUE
Pellet boilers UNI EN 303-5 - 6cm2 x kW
• If the ventilation intake is made in an adjacent
room directly connected with the outside, the hole
between the ventilation room and the installation
room must be doubled at each passage (see
UNI10683). The hole to the external environment
must be equal to what is prescribed in the previous
point. Pay attention to any other suction systems
to prevent that negative pressure occurs in the
ventilation room and/or installation room.
• The maximum pressure difference allowed
between the outside and the installation room is
always and in any case 4Pa (that is, room negative
pressure).
• Ventilation air for the installation rooms cannot
be taken from rooms exposed to the risk of re,
e.g., garages, bedrooms, bathrooms and toilets,
shared premises.
• Combustion air cannot be drawn from crawl
spaces, or from less than half a metre from the
return/delivery vents of the crawl spaces.
• Ventilation holes can be closed with grids as long
as they do not reduce their useful section, and do
not hinder ordinary maintenance operations.
• The ventilation inlets must NEVER be obstructed
by any type of material, not even partially, which
could jeopardize the occupants’ health.
• The ventilation outlets must comply with the
relevant technical standards and any current local
and national regulations, specically with regard
to their section, position, type and characteristics.
• Ventilation holes are not made necessary in the
case of installation of airtight appliances (which
are equipped with their specic ventilation duct).
• In the presence of a CMV system (Controlled
Mechanical Ventilation), installation with
combustion air drawn from the installation room
is not permitted - see the "Ventilation ducting"
chapter;
• The manufacturer is not liable for any claim for
compensation for damages due to non-compliant
installation of the ventilation outlets with respect
to the above, and to the technical standards and
all the legislative provisions in force.
3.2.1 VENTILATION DUCTING
• To channel combustion air from the outside to
a traditional appliance or, in case of airtight
installation (hermetic appliance), it is necessary to
install a ventilation duct.
• The ventilation duct must have a section equal to
or greater than the combustion air connection of
the appliance.
• The ventilation duct must have the same section
along its entire length. Narrowing the duct is only