Eaton Green Motion XCI000411 handleiding
Handleiding
Je bekijkt pagina 48 van 107

Figure 25. Load balancing algorithm outputs
Tag Description
1
Green Motion Building EV charger Master
2
Green Motion Building EV charger Node
3
Energy meter
4
Maximum available current for charging (= Maximum current capacity of building – Energy meter reading)
5
Optimal output currents (depending on the Eaton load balancing algorithm)
5
1
4
3
5
5
2
2
2
Static load balancing: The maximum available current is divided over the EV chargers according to the Eaton load
balancing algorithm. The maximum available current is a FIXED VALUE depending on the electrical installation.
Dynamic load balancing: The maximum available current is divided over the EV chargers according to the Eaton
load balancing algorithm. The maximum available current is a DYNAMIC VALUE updated according to the building
consumption monitored in real-time with an energy meter (EM).
(
Phase balancing: Limits current differences between phases. Large deviations in load per phase can cause grid
instability and problems with the powered devices.
Maximum available current = Maximum current - Maximum other loads - Margin
(static) (building) (building)
Maximum available current = Maximum current - other loads - Margin
(dynamic) (building) (monitored by energy meter)
48
GREEN MOTION BUILDING INSTALLATION MANUAL MN191028EN April 2024 www.eaton.com
Bekijk gratis de handleiding van Eaton Green Motion XCI000411, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
Merk | Eaton |
Model | Green Motion XCI000411 |
Categorie | Niet gecategoriseerd |
Taal | Nederlands |
Grootte | 16416 MB |