7.3 UPS shutdown
To shut down the UPS:
Press the button on the front panel for three seconds.
A confirmation message will appear. When confirmed, the UPS starts to beep and shows a status of "UPS shutting OFF...".
The UPS thentransfers to Standby mode, and the indicator turns off.
7.4 Operating modes
The Eaton5PX front panel indicates the UPS status through the UPS indicators located above the LCD screen.
Normal mode
When the green sinewave symbol is illuminated, the UPS is providing protected AC power output.The UPS monitors and
charges the batteries as needed and providespower protection to yourequipment.
Battery mode
When the UPS is operating during a power outage, the alarm beeps once every ten seconds and theindicator illuminates
solid. The necessary energy is provided by the battery.
When the utility power returns, the UPS transfers to Normal mode operation while the battery recharges.
If battery capacity becomes low while in Battery mode, the audible alarm beeps once every three seconds.
This warning is approximate, and the actual time to shutdown may vary significantly; gracefully shutdown all applications
on connected equipment due to imminent UPS shutdown.
When utility power is restored after the UPS shuts down, the UPS automatically restarts.
Low-battery warning
The indicator illuminates solid.
The audio alarm beeps every three seconds.
The remaining battery power is low. Shut down all applications on the connected equipment becauseautomatic UPS
shutdown is imminent.
End of battery backup time
LCD displays "End of backup time".
All the LEDs go OFF.
The audible alarm stops.
7.5 Return of AC input power
Following an outage, the UPS restarts automatically when AC input power returns (unless the restart functionhas been
disabled) and the load is supplied again.
7.6 Configuring battery settings
Automatic battery test
Automatic battery tests are done every week in constant charging mode and at each cycle in ABM® mode. Thetests
frequency can be modified.
During the test, the UPS transfers to Battery mode and discharges the batteries for 10 seconds under load.
Battery mode is not displayed and battery low alarm does not activate during a battery test.
The battery test may be postponed due to bad conditions, or failed if battery is not ok.
Low battery warning
During discharge, the low battery alarm is activated if the remaining runtime goes below 3 minutes or less than the
setting capacity threshold (0% by default).
This threshold can be modified.
External battery setting
Bekijk gratis de handleiding van Eaton 5PX Gen2, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
Merk | Eaton |
Model | 5PX Gen2 |
Categorie | Niet gecategoriseerd |
Taal | Nederlands |
Grootte | 5690 MB |
Caratteristiche Prodotto
Kleur van het product | Zwart, zilver |
Gewicht | 40400 g |
Breedte | 438 mm |
Diepte | 603 mm |
Hoogte | 85.5 mm |