3.6.1 PV Module Selection:
3.6.2 PV Module Wire Connection:
When selecting proper PV modules, please be sure to consider below parameters:
1) Open circuit Voltage (Voc) of PV modules can not exceed max.PV Input Voltage of
inverter.
2) Open circuit Voltage (Voc) of PV modules should be higher than min.PV Input Voltage of inverter.
3) The PV modules used to connected to this inverter shall be Class A rating certified according
to lEC 61730.
- 17 -
1. Switch the Grid Supply Main Switch(AC)OFF.
2. Switch the DC lsolator OFF.
3. Assemble PV input connectors to the inverter.
Safety Hint:
Before connecting to inverter, please make sure that the open circuit voltage of
PV strings haven't exceeded the max.PV input voltage of the inverter.
Safety Hint:
Before connection, please make sure the polarity of PV array matches the
"DC+" and "DC-" symbols.
Pic 5.1 DC+ male connector
Pic 5.2 DC- female connector
Chart 3-5
PV Input Voltage
Inverter Model
PV Array MPPT Voltage Range
No. of MPP Trackers
No. of Strings MPP Tracker
650V (180V-1000V)
150V-850V
2+2+2+2+2+2
6
60kW 70kW 80kW
75kW