3.8 Earth Connection(mandatory)
Ground cable shall be connected to ground plate on grid side, this prevents electric shock if the
original protective conductor fails.
3.9 Data logger Connection
For the configuration of data logger, please refer to the user manual of data logger. Wi-Fi logger is
not the only option, If the installation location does not have Wi-Fi signal or the signal is weak,
you can also choose a data logger that communicates via other interfaces.
The conductor should be made of the same metal as the phase conductors.
Earth Connec�on (Copper wires) (bypass)
Earth Connec�on (Copper wires)
Warning:
Inverter has built-in leakage current detection circuit,The type A RCD can be
connected to the inverter for protection according to the local laws and regula-
tions.If an external leakage current protection device is connected to the grid port
of inverter, please refer to section 3.11, its operating current must be equal to 300
mA or higher, otherwise inverter may not work properly.
Model
25/29.9/30kW
Wire Size Cross section(mm )
2
Torque value(max)
4AWG 16 4.0Nm
Model Wire Size Cross section(mm )
2
Torque value(max)
25/29.9/30kW 4AWG 16 3.4Nm