Solar Arc Fault ON
Clear Arc_Fault
System selfcheck
CEI Report
0ms
2000:1
Backup Delay
Advanced Function
Func
Set1
DRM
Gen peak-shaving
CT Ratio
Signal Island Mode
Asymmetric phase feeding
5.10 Advanced Function Setup Menu
Signal island mode:
If "Signal island mode" is checked and When inverter is in off-grid mode, the relay on the Neutral line of
load port will switch on, then the N line of load port will bind to ground.
Asymmetric phase feeding:
When the loads connected to the Load port have an unbalanced distribution on the three phases
and the inverter is working in on-grid mode, enabling this function will ensure an equal power absorption from the three phases
of grid.
L1 L2 L3 N
Load port
Inverter
Shell
Relay
Ground cable
Parallel: Enable this function when several same model hybrid
inverters are connecting in parallel.
Master: Select any hybrid inverter in the parallel system as the
master inverter, and the master inverter needs to manage the
working mode of the parallel system.
Slave: Set the other inverters managed by the master inverter
as slave inverter.
Modbus SN: The Modbus address of each inverter, should be
different.
Ex_Meter For CT:
when using zero-export to CT mode,
the hybrid inverter can select EX_Meter For CT function
and use the different meters.e.g.CHNT and Eastron.
Parallel
Master
Slave
00
Modbus SN
Paral.
Set3
EX_Meter For CT
Meter Select
0/3No Meter
CHNT
Eastron
Solar Arc Fault ON:
This function is only applicable to the US market
and customized customers.
System selfcheck:
Disable. this is only for factory.
Gen Peak-shaving:
Limit the maximum output power of the
generator to the set rated power on "GEN PORT USE" page, the rest of
power consumption will be provided by inverter to ensure that the
generator will not overload.
DRM:
Demand response mode, receive external commands for active
power scheduling and reactive power scheduling.
Backup Delay:
When the grid cuts off, the inverter will output power
after the set time.
For example, backup delay: 600s. the inverter will give output power
after 600s when the grid cuts off.
Note: for some old FW version, this function is not available.